Operating Instructions Safety Switch CES-I-AR-U-C04

29

Operating distances
Operating distance for center offset m = 0

(only in combination with actuator CES-A-BBN-C04 from approach direction A or B)

Parameter

Value

Unit

min.

typ.

max.

Switch-on distance

-

15

-

mm

Assured switch-on distance s

ao

1)

10

-

-

Switching hysteresis

1)

1

2

-

Assured switch-off distance s

ar

- in x/z direction

- in y direction

-

-

-

-

40

60

1) On approach in Z direction

Operating distance for center offset m = 0

(only in combination with actuator CES-A-BBN-C04 from approach direction C or D)

Parameter

Value

Unit

min.

typ.

max.

Switch-on distance

-

11

-

mm

Assured switch-on distance s

ao

1)

6

-

-

Switching hysteresis

1)

1

2

-

Assured switch-off distance s

ar

- in x/z direction

- in y direction

-

-

-

-

40

60

1) On approach in x direction

Typical operating distance in approach direction A

(Only in combination with actuator CES-A-BBN-C04)

Figure 7: Typical operating distance

Approach direction

A

B

Approach direction

C

D

-25

-30

X

10

5

15

20

-20

-25

-30

-40

-35

-15

-10

-5

-10

20

25

30

15

10

40

35

5

Y

-5

-15

-20

Z

10

15

20

25

5

30

For a side approach direction (y direction) for the actuator and safety switch,

a minimum distance of s = 6 mm must be maintained so that the operating distance

of the side lobes is not entered.