Operating Instructions Safety Switch CES-AP-C01-CH
18
Typical system times
Ready delay: After switching on, the unit carries out a self-test for 500 ms. The
system is ready for operation only after this time.
Switch-on time of safety outputs: The max. reaction time from the moment
when the actuator is at the operating distance (safety door closed) to the moment
when the safety outputs switch on T
on
is 400 ms.
Risk time according to EN 60947-5-3: If an actuator moves outside the op-
erating distance, the safety outputs OA and OB are deactivated after a maximum
of 260 ms.
Time difference: The safety outputs OA and OB switch with a slight time offset.
They have the same signal state at the latest after a difference time of 10 ms.
Clock pulses at the safety outputs: The device generates its own clock signal
on the output lines OA/OB. A downstream control system must tolerate these clock
pulses, which may have a length of up to 400 µs.
This can usually be set up in the control systems by parameter assignment. If
parameter assignment is not possible for your control system or if shorter clock
pulses are required, please contact our support organization.
Dimension drawing
40 40,
5
56,5
13
34
20,
5
M12x
1
7
47
30
Ø5,5
LEDs