Operating Instructions Safety Switch CES-AP-C01-CH
13
Connection
Note:
The connection examples show the 8-pin version. The 5-pin version is connected
analogously (see section Connector assignment, safety switch CES-AP-C01).
Connect the device as shown in Figure 2. The DIA output can be connected to a
control system as a monitoring output.
The switch can be reset via the RST input. To do this, a voltage of 24 V is applied
to the RST input for at least 3 seconds. If input RST is not used in your application,
it should be connected to 0 V.
Important!
The subsystem CES-AP complies with PL e in accordance with EN 13849-1. To
integrate the subsystem in a category 3 or 4 structure, it is necessary to monitor
the downstream load (the feedback loop must be monitored).
These examples show only an excerpt that is relevant for connection of the CES
system. The example illustrated here does not show complete system planning.
The user is responsible for safe integration in the overall system.
GND
DC 24 V
-F1
CES-AP-C
n.c.
1
UB
2
O
A
3
O
B
4
M12 plug-connector
(8-pin)
DIA
5
n.c.
6
0V
7
RS
T
8
-V1
-K1
-V2
-K2
L1
M
3
~
-M1
L2
L3
Figure 2: Connection example CES-AP-C