System status table, Operating instructions safety switch ces-ap-c01-ch – EUCHNER CES-AP-C01-CH (Multicode) User Manual
Page 16
Operating Instructions Safety Switch CES-AP-C01-CH
16
System status table
Operating mode
Actuator/door posi
-
tion
Safety outputs OA and OB
LED indicator,
output
State
ST
ATE (gr
een)
DIA (r
ed)
Normal operation
closed
on
Normal operation, door closed
closed
on
flashes
quickly
2 Hz
Normal operation, door closed, actuator in limit range
¨
Re-adjust door
open
off
1 x
Normal operation, door open
Fault display
closed
off
3 x
Defective actuator (e.g. fault in code or code not readable)
X
off
4 x
Output error (e.g. short circuits, loss of switching ability)
X
off
5 x
Internal fault (e.g. component faulty, data error)
Key to symbols
LED not illuminated
LED illuminated
10 Hz (8 s)
LED flashes for 8 seconds at 10 Hz
3 x
LED flashes three times, and this is then repeated
X
Any state
After the cause has been remedied, faults can generally be reset by opening
and closing the door. If the fault is still displayed afterward, briefly interrupt the
power supply. Please contact the manufacturer if the fault could not be reset after
restarting.
Important!
If you do not find the displayed device status in the System status table, this indi-
cates an internal device fault. In this case, you should contact the manufacturer.