Technical data, Typical operating distance – EUCHNER CES-FD-AP-U-01-xxx (Unicode) User Manual
Page 22
Operating Instructions Field Evaluation Unit CES-FD-AP-.-01-…
22
Technical data
Parameter
Value
Unit
min.
typ.
max.
Housing material
Nickel-plated CuZn housing sleeve
Plastic PBT GF20 cap
Dimensions
M12 x 1, length 38
mm
Weight
0.2
kg
Ambient temperature
-20
-
+70
°C
Ambient pressure (only of active face in installed condition)
-
-
10
bar
Degree of protection
IP67
Installation position
Any
Method of operation
Inductive
Power supply
Via evaluation unit
In combination with actuator CES-A-BMB on field evaluation unit CES-FD-AP-.-01-…
Assured switch-off distance S
ar
-
-
10
mm
Operating distance for center offset m = 0
1)
- Switch-on distance
-
5
-
- Assured switch-on distance S
ao
3.4
-
-
- Switching hysteresis
0.05
0.2
-
Connection
M8 plug connector (snap-action and screw terminals), 3-pin
Connection cable
-
-
0.7
m
1) These values apply for surface installation of the read head in steel.
Typical operating distance
(Only in combination with field evaluation unit CES-FD-AP-.-01-… and actuator
CES-A-BMB)
Figure 5: Typical operating distance
Note
A minimum distance of s = 1.2 mm must be maintained.
The read distance may vary depending on the installation situation