Technical data, Typical operating distance – EUCHNER CES-FD-AP-U-01-xxx (Unicode) User Manual

Page 22

background image

Operating Instructions Field Evaluation Unit CES-FD-AP-.-01-…

22

Technical data

Parameter

Value

Unit

min.

typ.

max.

Housing material

Nickel-plated CuZn housing sleeve

Plastic PBT GF20 cap

Dimensions

M12 x 1, length 38

mm

Weight

0.2

kg

Ambient temperature

-20

-

+70

°C

Ambient pressure (only of active face in installed condition)

-

-

10

bar

Degree of protection

IP67

Installation position

Any

Method of operation

Inductive

Power supply

Via evaluation unit

In combination with actuator CES-A-BMB on field evaluation unit CES-FD-AP-.-01-…
Assured switch-off distance S

ar

-

-

10

mm

Operating distance for center offset m = 0

1)

- Switch-on distance

-

5

-

- Assured switch-on distance S

ao

3.4

-

-

- Switching hysteresis

0.05

0.2

-

Connection

M8 plug connector (snap-action and screw terminals), 3-pin

Connection cable

-

-

0.7

m

1) These values apply for surface installation of the read head in steel.

Typical operating distance

(Only in combination with field evaluation unit CES-FD-AP-.-01-… and actuator

CES-A-BMB)

Figure 5: Typical operating distance

Note

A minimum distance of s = 1.2 mm must be maintained.
The read distance may vary depending on the installation situation

2

4

6

6

8

8

X

8

6

4

2

2

4

6

8

8

6

Y

Z