Fuse protection for power supply, Requirements for connection cables – EUCHNER CES-FD-AP-U-01-xxx (Unicode) User Manual

Page 10

background image

Operating Instructions Field Evaluation Unit CES-FD-AP-.-01-…

10

Fuse protection for power supply

The power supply must be provided with fuse protection depending on the current

required for the outputs. The following rules apply:
Max. current consumption of a switch I

max

I

max

= I

UB

+ I

OD

+ I

FO1A+FO1B

I

UB

= Switch operating current (45 mA)

I

OD

= Monitoring output load current (max. 50 mA)

I

FO1A+FO1B

= Load current safety outputs FO1A + FO1B (2 x max. 150 mA)

Requirements for connection cables

Caution!

Risk of damage to equipment or malfunctions as a result of incorrect connec-
tion cables.

Ì

Use connection components and connection cables from EUCHNER

Ì

On the usage of other connection components, the requirements in the fol-
lowing table apply. EUCHNER provides no warranty for safe function in case
of failure to comply with these requirements.

Ì

The connection cable for the field evaluation unit must not be longer than
180 m in total.

Ì

The connection cable from the field evaluation unit to the read head is only
allowed to be extended with the aid of the extension (order no. 115464).

Ì

The read head cable must not be longer than 0.7 m in total.

Observe the following requirements with respect to the connection cables for the

connection of the device:

Parameter

Value

Unit

Conductor cross-section min.

0.14

mm²

R max.

150

W

/km

C max.

120

nF/km

L max.

0.65

mH/km

Recommended cable type

LIYY 8x or 5x0.14 mm²