Typical system times
Ready delay: After switching on, the unit carries out a self-test. The system is
ready for operation only after this time (0.5 s).
Switch-on time of safety outputs: The max. reaction time from the moment
when the actuator is at the operating distance (safety door closed) to the moment
when the safety outputs switch on T
on
is 400 ms.
Risk time according to EN 60947-5-3: If an actuator moves outside the
operating distance, the safety outputs FO1A and FO1B are deactivated after a
maximum of 260 ms.
Difference time: The safety outputs FO1A and FO1B switch with a slight delay
in relation to each other. They have the same signal state at the latest after a dif-
ference time of 10 ms.
Test pulses at the safety outputs: The device generates its own clock signal on
the output lines FO1A/FO1B. A downstream control system must tolerate these
test pulses, which may have a duration of up to 0.4 ms.
This can usually be set up in the control systems by parameter assignment. If
parameter assignment is not possible for your control system or if shorter test
pulses are required, please contact our support organization.
Read head CES-A-LMN-SC
Ì
Cylindrical design M12
Ì
M8 plug connector (snap-action and screw terminals)
Dimension drawing
17
5
32
19
,7
R eading distance s
C
en
tre
o
ffs
et
m
connected
35
4
8
30
M
12
x1
M
8x
1
37
1)
1)
Active face
1) Clear zone (area of the active face without metal housing)