Operating Instructions Field Evaluation Unit CES-FD-AP-.-01-…

17

System status table for version Multicode

Operating mode

Actuator/ guar

d position

Safety outputs FO1A and FO1B

LED indicator

output

State

ST

ATE (gr

een)

DIA (r

ed)

Normal operation

closed

on

Normal operation, door closed

closed

on

flashes

quickly

2 Hz

Normal operation, door closed, actuator in limit range

¨

Re-adjust door

open

off

1 x

Normal operation, door open

Fault display

X

off

Fault on the power supply (e.g. Switch-off pulse duration of clocked power supply too long)

closed

off

3 x

Defective actuator (e.g. fault in code or code not readable)

X

off

4 x

Output error (e. g. short circuits, loss of switching ability)

X

off

5 x

Internal fault (e.g. component faulty, data error)

Key to symbols

LED not illuminated

LED illuminated

10 Hz (8 s)

LED flashes for 8 seconds at 10 Hz

3 x

LED flashes three times, and this is then repeated

X

Any state

After the cause has been remedied, faults can generally be reset by opening and

closing the door. If the fault is still displayed afterward, use the reset function or

briefly interrupt the power supply. Please contact the manufacturer if the fault could

not be reset after restarting.

Important!

If you do not find the displayed device status in the System status table, this indi-
cates an internal device fault. In this case, you should contact the manufacturer.