Functional check
Warning! Danger of fatal injury as a result of faults
in installation and functional check.
Before carrying out the functional check, make sure
that there are no persons in the danger area.
Observe the valid accident prevention regulations.
After installation and any fault, the safety function must
be fully checked. Proceed as follows:
Mechanical function test
The actuator must slide easily into the actuating head.
Close the safety guard several times to check the
function.
Electrical function test
1. Switch on operating voltage.
2. Close all safety guards.
Guard locking by solenoid force: Activate guard
locking.
The machine must not start automatically.
It must not be possible to open the safety guard.
3. Enable operation in the control system.
It must not be possible to deactivate the guard locking
as long as operation is enabled.
4. Disable operation in the control system and deactivate
guard locking.
The safety guard must remain locked until there is no
longer any risk of injury.
It must not be possible to start the machine as long as
the guard locking is deactivated.
Repeat steps 2 - 4 for each safety guard.
Illustration: Actuator inserted and locked
Inspection and service
If damage or wear is found, the complete switch
and actuator assembly must be replaced.
Replacement of individual parts or assemblies is
not permitted!
No servicing is required, but regular inspection of the
following is necessary to ensure trouble-free long-term
operation:
correct switching function
secure mounting of components
dirt and wear
sealing of cable entry
loose cable connections or plug connectors.
Note:The year of manufacture can be seen in the bottom,
right corner of the rating plate.
Exclusion of liability under the following
circumstances
incorrect use
non-compliance with safety regulations
installation and electrical connection not performed by
authorized personnel
failure to perform functional checks.
EC declaration of conformity
The manufacturer named below herewith declares that
the product fulfills the provisions of the directive(s) listed
below and that the related standards have been applied.
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen, Germany
Directives applied:
Machinery directive 2006/42/EC
Standards applied:
EN 60947-5-1:2004 + Cor.:2005 + A1:2009
EN 1088:1995+A2:2008
Leinfelden, July 2010
Dipl.-Ing. Michael Euchner
Director
Duc Binh Nguyen
Authorized representative empowered to draw up
documentation
The signed EC declaration of conformity is included with
the product.
Technical data
Parameters
Value
Housing material
Reinforced
thermoplastic
Degree of protection
acc. to IEC 60529
IP67
Installation position
Any
Mechanical life
1 x 10
6
operating cycles
Ambient temperature
-25 °C ... +50 °C
Approach speed, max.
0.05 ... 1.0 m/s
Actuation frequency, max.
900 / h
Actuating force, max.
at 20 °C
5 N
Extraction force (not locked)
10 N
Retention force
1 N
Locking force F
Zh
according to
500 N
GS-ET-19 (in locked position)
(100 N with actuator Q-WT)
Weight
Approx. 0.55 kg
Switching principle
Slow-action switching contact
Contact material
Silver alloy, gold flashed
Connection type
Connection cable 5 m
Rated insulation voltage
Safety contact SK
U
i
= 250 V
Monitoring contact ÜK
U
i
= 150 V
Rated impulse
U
imp
= 2.5 kV
withstand voltage
(1.5 kV between the contacts)
Rated short-circuit current
100 A
Degree of contamination
(external, acc. to EN 60947-1)
3 (industrial)
Switching current, min., at 24 V 1 mA
Switching voltage, min.
at 10 mA
12 V
Utilization category
AC-15
1 A
125 V
acc. to IEC 60947-5-1
DC-13
1 A
24 V
Conventional
thermal current I
th
2.5 A
Short circuit protection
2 A gG
Solenoid operating voltage
DC 24 V(+10%/-15%)
Solenoid duty cycle ED
100 %
Solenoid power consumption
2.7 W
Technical data as per TÜV and UL
Utilization category
Safety contact U
i
300 V
AC-15 0.75A/240VAC: Pilot Duty
DC-13 0.27A/250VDC: Pilot Duty
Monitoring contact U
i
150 V
AC-15 1A/125VAC: Pilot Duty
DC-13 0.22A/125VDC: Pilot Duty
Reliability figures according to EN ISO 13849-1
B
10d
2 x 10
6
Figure 3: Switching elements and terminal assignment
OG
21
BN
BN/WH
BU
12
11
SK
A1
(-)
BK
(+)
A2
WH
41
42
BU/WH
PK/WH
PK
51
52
32
31
22
OG/WH
ÜK
0302G
41
WH
A2
(+)
BK
(-)
A1
ÜK
11
12
BU
BN/WH
BN
21
OG
OG/WH
22
33
34
54
53
PK
PK/WH
BU/WH
42
SK
1211G
41
WH
A2
(+)
BK
(-)
A1
ÜK
11
12
BU
BN/WH
BU/WH
BN
21
OG
OG/WH
22
33
34
52
51
PK
GY
PK/WH
GY/WH
42
SK
1202SG
41
WH
A2
(+)
BK
(-)
A1
ÜK
11
12
BU
BN/WH
BU/WH
BN
21
OG
OG/WH
22
33
34
54
53
PK
GY
PK/WH
GY/WH
42
SK
1211SG