Operating Instructions Safety Switch TQ...

Subject to technical modifications; no r

esponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG

103787-06-02/11 (translation of the original operating instructions)

Functional check

Warning! Danger of fatal injury as a result of faults
in installation and functional check.

Before carrying out the functional check, make sure
that there are no persons in the danger area.
Observe the valid accident prevention regulations.

After installation and any fault, the safety function must
be fully checked. Proceed as follows:

Mechanical function test

The actuator must slide easily into the actuating head.
Close the safety guard several times to check the
function.

Electrical function test

1. Switch on operating voltage.

2. Close all safety guards.

Guard locking by solenoid force: Activate guard
locking.

The machine must not start automatically.

It must not be possible to open the safety guard.

3. Enable operation in the control system.

It must not be possible to deactivate the guard locking
as long as operation is enabled.

4. Disable operation in the control system and deactivate

guard locking.

The safety guard must remain locked until there is no
longer any risk of injury.

It must not be possible to start the machine as long as
the guard locking is deactivated.

Repeat steps 2 - 4 for each safety guard.

Illustration: Actuator inserted and locked

Inspection and service

If damage or wear is found, the complete switch
and actuator assembly must be replaced.

Replacement of individual parts or assemblies is
not permitted!

No servicing is required, but regular inspection of the
following is necessary to ensure trouble-free long-term
operation:

correct switching function

secure mounting of components

dirt and wear

sealing of cable entry

loose cable connections or plug connectors.

Note:The year of manufacture can be seen in the bottom,
right corner of the rating plate.

Exclusion of liability under the following
circumstances

incorrect use

non-compliance with safety regulations

installation and electrical connection not performed by
authorized personnel

failure to perform functional checks.

EC declaration of conformity

The manufacturer named below herewith declares that
the product fulfills the provisions of the directive(s) listed
below and that the related standards have been applied.

EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen, Germany

Directives applied:

Machinery directive 2006/42/EC

Standards applied:

EN 60947-5-1:2004 + Cor.:2005 + A1:2009

EN 1088:1995+A2:2008

Leinfelden, July 2010

Dipl.-Ing. Michael Euchner
Director

Duc Binh Nguyen
Authorized representative empowered to draw up
documentation

The signed EC declaration of conformity is included with
the product.

Technical data

Parameters

Value

Housing material

Reinforced
thermoplastic

Degree of protection

acc. to IEC 60529

IP67

Installation position

Any

Mechanical life

1 x 10

6

operating cycles

Ambient temperature

-25 °C ... +50 °C

Approach speed, max.

0.05 ... 1.0 m/s

Actuation frequency, max.

900 / h

Actuating force, max.

at 20 °C

5 N

Extraction force (not locked)

10 N

Retention force

1 N

Locking force F

Zh

according to

500 N

GS-ET-19 (in locked position)

(100 N with actuator Q-WT)

Weight

Approx. 0.55 kg

Switching principle

Slow-action switching contact

Contact material

Silver alloy, gold flashed

Connection type

Connection cable 5 m

Rated insulation voltage

Safety contact SK

U

i

= 250 V

Monitoring contact ÜK

U

i

= 150 V

Rated impulse

U

imp

= 2.5 kV

withstand voltage

(1.5 kV between the contacts)

Rated short-circuit current

100 A

Degree of contamination

(external, acc. to EN 60947-1)

3 (industrial)

Switching current, min., at 24 V 1 mA

Switching voltage, min.

at 10 mA

12 V

Utilization category

AC-15

1 A

125 V

acc. to IEC 60947-5-1

DC-13

1 A

24 V

Conventional

thermal current I

th

2.5 A

Short circuit protection

2 A gG

Solenoid operating voltage

DC 24 V(+10%/-15%)

Solenoid duty cycle ED

100 %

Solenoid power consumption

2.7 W

Technical data as per TÜV and UL

Utilization category

Safety contact U

i

300 V

AC-15 0.75A/240VAC: Pilot Duty
DC-13 0.27A/250VDC: Pilot Duty

Monitoring contact U

i

150 V

AC-15 1A/125VAC: Pilot Duty
DC-13 0.22A/125VDC: Pilot Duty

Reliability figures according to EN ISO 13849-1

B

10d

2 x 10

6

Figure 3: Switching elements and terminal assignment

OG

21

BN

BN/WH

BU

12

11

SK

A1

(-)

BK

(+)

A2

WH

41

42

BU/WH

PK/WH

PK

51

52

32

31

22

OG/WH

ÜK

0302G

41

WH

A2

(+)

BK

(-)

A1

ÜK

11

12

BU

BN/WH

BN

21

OG

OG/WH

22

33

34

54

53

PK

PK/WH

BU/WH

42

SK

1211G

41

WH

A2

(+)

BK

(-)

A1

ÜK

11

12

BU

BN/WH

BU/WH

BN

21

OG

OG/WH

22

33

34

52

51

PK

GY

PK/WH

GY/WH

42

SK

1202SG

41

WH

A2

(+)

BK

(-)

A1

ÜK

11

12

BU

BN/WH

BU/WH

BN

21

OG

OG/WH

22

33

34

54

53

PK

GY

PK/WH

GY/WH

42

SK

1211SG