Verify the retrofit, Configure the cem3 – ETC Sensor+ CE Rack (ESR+) CEM+ to CEM3 Retrofit User Manual

Page 15

background image

2

The Retrofit

13

Verify the Retrofit

Step 1:

Put the dimmer modules back in the rack in the correct/original order.

Step 2:

Put the CEM3 in the rack.

Step 3:

Power up the rack. Before removing dimmer or control modules for service,

de-energize main feed to dimmer rack and follow appropriate Lockout/

Tagout procedures as described in NFPA Standard 70E. It is important to

note that electrical equipment such as dimmer racks can present an arc

flash safety hazard if improperly serviced. This is due to available large

short circuit currents on the feeders of the equipment. Any work on

energized equipment must comply with OSHA Electrical Safe Working

Practices.

Step 4:

Check that the CEM3 powers up and the rack fan turns on. (The only rack errors

should be a lack of DMX on the ports if the DMX source is not present.)

Configure the CEM3

Step 1:

Configure the rack to reflect the dimmer module types installed. Verify that the

rack type is correct (CEM3 should have determined this from the DIP switch

settings - see

Backplane Settings, page 9

). Configuration of the CEM3 is done

using the front face panel interface. See the CEM3 Quick Guide that ships with

the CEM3 for more information.

Step 2:

Configure the data types that will be used (DMX and sACN) including the rack

patch.