Specifications – Det-Tronics EQ3750ASH EQP Addressable Smoke & Heat (ASH) Module User Manual
Page 5
4.2
95-8654
5
passive and Active Integrity Checks
During a passive integrity check no alerts will be sent to
the ASH Module or EQP Controller. All indications will be
handled by the local LEDs on the loop devices.
An active integrity check will be indicated on the ASH
Module, the controller, and the loop devices as an active
alarm. A fault indication will be generated if the integrity
check fails.
Automatic Integrity Check (AIC)
When enabled, an automatic integrity check is performed
every 24 hours for all the loop devices. The ASH Module
controls the initiating of the integrity check for each loop
device, one at a time. The AIC is disabled by default and
the start time is configurable within the ASH Apollo editor
in S
3
. If a device is currently in the middle of an AIC,
and the AIC becomes disabled, that particular device
will conclude its test, but no new test will begin. Manual
integrity check requests are ignored during an AIC, and
if a manual integrity check is in progress when an AIC is
scheduled, the AIC will be delayed.
Manual Integrity Check (MIC)
The manual integrity check can be performed individually
for a single loop device, or globally for all devices on a
single ASH Module.
Note
If a manual integrity check is already in progress,
a new request of either an AIC or MIC will be
ignored.
Integrity Check Faults
When an integrity check fails, the loop device fault LED
will be activated. The fault indication will remain until an
ASH Module reset is performed, or until another integrity
check is done, and passes.
Note
If there is an active alarm, any new integrity
check request is ignored. If an integrity check is
in progress and an alarm condition occurs, the
integrity check will be interrupted and the alarm
will be annunciated.
WALk TEST
The walk test is intended to verify the operation of the
loop devices. A walk test is activated by physically
walking up to each device, one at a time, and setting
them into an alarm condition. Alternatively, a walk test
can be activated from the ASH Module’s point display
within S
3
. The test verifies that each device does indeed
go into an alarm. The alarm condition is logged into the
EQP Controller, but the controller takes no further action.
speciFications
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc.
INPUT CURRENT (Maximum)—
690 mA.
LOOP CURRENT (Maximum)—
225 mA.
POwER CONSUMPTION (Maximum)—
11 Watts.
wIRING (Maximum)—
12 AWG
14 AWG
16 AWG
18 AWG
4 mm
2
2.5 mm
2
1.5 mm
2
0.75 mm
2
Feet
15500
9800
6200
3900
Meters
4700
3000
1900
1200
TEMPERATURE RANGE—
Operating:
–40°F to +185°F (–40°C to +85°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
DIMENSIONS—
See Figure 6.
SHIPPING wEIGHT—
2.7 pounds (1.22 kilograms)
A2536
6.31
(16.0)
4.31
(10.9)
4.56
(11.5)
2.0
(5.08)
Figure 6—Dimensions of the ASH Module in Inches (Centimeters)