FM Approval and performance Report – Continued

FIELD OF vIEw

very high Sensitivity

Medium Sensitivity

high Sensitivity

Fuel

Size

Distance

feet (m)

horizontal

(degrees)

Typical

Response Time

(seconds)

vertical

(degrees)

Typical

Response
(seconds)

Mode

n-Heptane

1 x 1 foot

42.5

(13)

+45

–45

2
2

+45

–30

2
2

Low Arc

Methane

32 inch

plume

50

(15.2)

+45

–45

2
2

+45

–30

2
2

Low Arc

Fuel

Size

Distance

feet (m)

horizontal

(degrees)

Typical

Response Time

(seconds)

vertical

(degrees)

Typical

Response
(seconds)

Mode

n-Heptane

1 x 1 foot

30

(9.1)

+45

–45

1
1

+45

–30

1
1

Standard

n-Heptane

1 x 1 foot

30

(9.1)

+45

–45

1
1

+45

–30

1
1

Hi Arc

n-Heptane

1 x 1 foot

30

(9.1)

+45

–45

2
2

+45

–30

2
2

Very Hi Arc

Methane

32 inch plume

40

(12.2)

+45

–45

1
1

+45

–30

1
1

Standard

Methane

32 inch plume

40

(12.2)

+45

–45

1
1

+45

–30

1
1

Hi Arc

Methane

32 inch plume

35

(10.7)

+45

–45

1
1

+45

–30

1
1

Very Hi Arc

Fuel

Size

Distance

feet (m)

horizontal

(degrees)

Typical

Response Time

(seconds)

vertical

(degrees)

Typical

Response
(seconds)

Mode

n-Heptane

1 x 1 foot

17.5

(5.3)

+45

–45

1
1

+45

–30

1
1

Standard

n-Heptane

1 x 1 foot

25

(7.6)

+45

–45

1
1

+45

–30

1
1

Hi Arc

Methane

32 inch plume

30

(9.1)

+45

–45

2
2

+45

–30

2
2

Standard

Methane

32 inch plume

30

(9.1)

+45

–45

1
1

+45

–30

1
1

Hi Arc