beautypg.com

Figure 11—ex d wiring option, Figure 12—ex e wiring option – Det-Tronics X2200 UV Flame Detector with Pulse Output User Manual

Page 16

background image

95-8552

5.3

14

A2162

FIRE ALARM PANEL

X2200 DETECTOR

ALARM

24 VDC

+

WIRING NOTES:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND

THE CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL

oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND

ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.

(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC

oi IS USED.)

4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION

FOR INSTALLATION DETAILS.

END OF

LINE DEVICE 4

oi TEST 3

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

PULSE OUT

COM FIRE2

N.O. FIRE2

N.C. FIRE2

COM FAULT1

N.O. FAULT1

24 VDC +

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

Figure 11—Ex d Wiring Option

A2163

FIRE ALARM PANEL

X2200 DETECTOR

ALARM

ALARM

24 VDC

+

WIRING NOTES:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND

THE CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL

oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND

ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.

(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC

oi IS USED.)

4 EOL RESISTOR SUPPLIED BY PANEL.

EOL

DEVICE 4

oi TEST 3

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

PULSE OUT

COM FIRE2

N.O. FIRE2

N.C. FIRE2

COM FAULT1

N.O. FAULT1

24 VDC +

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

Figure 12—Ex e Wiring Option