Det-Tronics X2200 UV Flame Detector with Pulse Output User Manual
Page 11

9
95-8552
5.3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
+
–
(A) +290 VDC
B - INPUT 1
B - INPUT 2
B - INPUT 3
B - INPUT 4
B - INPUT 5
B - INPUT 6
B - INPUT 7
B - INPUT 8
D1-1
oi DRIVER
D1-2
oi DRIVER
D1-3
oi DRIVER
D1-4
oi DRIVER
D1-5
oi DRIVER
D1-6
oi DRIVER
D1-7
oi DRIVER
D1-8
oi DRIVER
D2-1
oi DRIVER
D2-2
oi DRIVER
D2-3
oi DRIVER
D2-4
oi DRIVER
D2-5
oi DRIVER
D2-6
oi DRIVER
D2-7
oi DRIVER
D2-8
oi DRIVER
DMA OUT AVAILABLE
DMA OUT
DMA IN
DATA STROBE
DMA IN AVAILABLE
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
ZONE OUTPUT 1
ZONE OUTPUT 2
ZONE OUTPUT 3
ZONE OUTPUT 4
ZONE OUTPUT 5
ZONE OUTPUT 6
ZONE OUTPUT 7
ZONE OUTPUT 8
FIRE LOGIC “A”
FIRE LOGIC “B”
ALARM OUTPUT
EXTERNAL RESET/INHIBIT
OUTPUTS INHIBITED
FAULT OUTPUT
EXTERNAL ACCEPT
STATUS & DET. OUTPUT S1
STATUS & DET. OUTPUT S2
STATUS & DET. OUTPUT S3
STATUS & DET. OUTPUT S4
STATUS & DET. OUTPUT S5
STATUS & DET. OUTPUT S6
STATUS & DET. OUTPUT S7
STATUS & DET. OUTPUT S8
DATA BUS 0
DATA BUS 1
DATA BUS 2
DATA BUS 3
DATA BUS 4
DATA BUS 5
DATA BUS 6
DATA BUS 7
CHASSIS (EARTH) GND
J1-7
J1-15
J1-5
J1-13
J1-6
J1-14
J1-8
J1-16
J1-9
J1-17
J1-10
J1-18
J1-11
J1-19
J2
R7404 CONTROLLER
J1
10 TO 38 VDC
}
#2
#1
#19
#22
X2200
DETECTOR 1
#2
#1
#19
#22
#2
#1
#19
#22
X2200
DETECTOR 2
#2
#1
#19
#22
#2
#1
#19
#22
X2200
DETECTOR 3
#2
#1
#19
#22
#2
#1
#19
#22
X2200
DETECTOR 4
#2
#1
#19
#22
#2
#1
#19
#22
X2200
DETECTOR 5
#2
#1
#19
#22
#2
#1
#19
#22
X2200
DETECTOR 6
#2
#1
#19
#22
#2
#1
#19
#22
X2200
DETECTOR 7
#2
#1
#19
#22
#2
#1
#19
#22
X2200
DETECTOR 8
#2
#1
#19
#22
A2157
NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
24
VDC
+
–
62
63
64
TO J1-2
0.47 μF / 400 VDC
NON-POLARIZED
GROUND FAULT PROTECTED SYSTEMS
TERMINAL NO.
FUNCTION
1/11
DC– ("C" LEAD)
2/12
DC+ ("A" LEAD)
19
SIGNAL ("B" LEAD)
22
oi
("D" LEAD)
TERMINAL IDENTIFICATION FOR X2200
WITH PULSE OUTPUT.
NOTE: DO NOT CONNECT THE X2200 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
Figure 6—A Typical System, X2200 Detectors Wired to R7404 Controller