beautypg.com

Det-Tronics X3301 Multispectrum IR Flame Detector with HART User Manual

Page 14

background image

95-8577

12

3.1

oi MENU

1) Left

oi

Percentage of calibrated oi test signal returned by the left sensor. Reading should be

90

to

100

percent. If reading is below

90

percent, go to “Device Setup”, select “Calibration”,

and perform oi Calibration.

2) Middle

oi

Percentage of calibrated oi test signal returned by the middle sensor. Reading should be

90

to

100

percent. If reading is below

90

percent, go to “Device Setup”, select “Calibration”,

and perform oi Calibration.

3) Right

oi

Percentage of calibrated oi test signal returned by the right sensor. Reading should be

90

to

100

percent. If reading is below

90

percent, go to “Device Setup”, select “Calibration”,

and perform oi Calibration.

4)

oi Fail Count

Number of consecutive oi failures counted (one passed oi test resets the counter).

5) No.

oi Failures

Set (allowable) number of consecutive oi failures to produce a fault.

6)

oi Cal Active

oi calibration is in progress.

7)

oi Cal Fault An

oi calibration fault has occurred.

8) Manual

oi Active

A manual oi test is in progress.

9) Manual

oi Fail

The detector has failed the last manual oi test.

oi

Menu

1) Left

oi

2) Middle

oi

3) Right

oi

4)

oi Fail Count

5) No.

oi Failures

6)

oi Cal Active

7)

oi Cal Fault

8) Manual

oi Active

9) Manual

oi Fail

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X3301 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Status Info Menu

1) Warmup (Y/N)
2) Fire (Y/N)
3) Auto

oi Fault (Y/N)

4) Dim Detect Fault (Y/N)
5) Detect Disable Flt (Y/N)
6) Snsr Hdwr Fault (Y/N)
7) HIB Hdwr Fault (Y/N)
8) Int Comm Fault
9) Incompatible Flt
10) Voltage Fault (Y/N)
11) Hardware Menu
12)

oi Menu