Det-Tronics X3301 Multispectrum IR Flame Detector with HART User Manual
Page 14
95-8577
12
3.1
oi MENU
1) Left
oi
Percentage of calibrated oi test signal returned by the left sensor. Reading should be
90
to
100
percent. If reading is below
90
percent, go to “Device Setup”, select “Calibration”,
and perform oi Calibration.
2) Middle
oi
Percentage of calibrated oi test signal returned by the middle sensor. Reading should be
90
to
100
percent. If reading is below
90
percent, go to “Device Setup”, select “Calibration”,
and perform oi Calibration.
3) Right
oi
Percentage of calibrated oi test signal returned by the right sensor. Reading should be
90
to
100
percent. If reading is below
90
percent, go to “Device Setup”, select “Calibration”,
and perform oi Calibration.
4)
oi Fail Count
Number of consecutive oi failures counted (one passed oi test resets the counter).
5) No.
oi Failures
Set (allowable) number of consecutive oi failures to produce a fault.
6)
oi Cal Active
oi calibration is in progress.
7)
oi Cal Fault An
oi calibration fault has occurred.
8) Manual
oi Active
A manual oi test is in progress.
9) Manual
oi Fail
The detector has failed the last manual oi test.
oi
Menu
1) Left
oi
2) Middle
oi
3) Right
oi
4)
oi Fail Count
5) No.
oi Failures
6)
oi Cal Active
7)
oi Cal Fault
8) Manual
oi Active
9) Manual
oi Fail
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
X3301 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Status Info Menu
1) Warmup (Y/N)
2) Fire (Y/N)
3) Auto
oi Fault (Y/N)
4) Dim Detect Fault (Y/N)
5) Detect Disable Flt (Y/N)
6) Snsr Hdwr Fault (Y/N)
7) HIB Hdwr Fault (Y/N)
8) Int Comm Fault
9) Incompatible Flt
10) Voltage Fault (Y/N)
11) Hardware Menu
12)
oi Menu