Det-Tronics X3301 Multispectrum IR Flame Detector with HART User Manual
Page 13
11
95-8577
3.1
HARDWARE MENU
1) Heater Power
Actual heater power (
0
to
100%
). Heater prevents condensation and icing on the detector
optics.
2) Heater Setpoint
Maximum amount of heater power allowed (in percent of full power).
3) Temperature
Actual internal temperature of detector.
4) Temp Setpoint
Internal target temperature that the heater will attempt to maintain (in degrees C).
5) Temp Range Fault
Detector integral temperature out of range — Operating range: –
40°
F to +
167°
F
(–
40°
C to +
75°
C).
6) Voltage
Actual detector supply voltage (must be
18
to
30
Vdc).
7) Volt Range Fault
Supply voltage is out of range. Operating voltage must be
18
to
30
Vdc.
Hardware Menu
1) Heater Power
2) Heater Setpoint
3) Temperature
4) Temp Setpoint
5) Temp Range Fault
6) Voltage
7) Volt Range Fault
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
X3301 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Status Info Menu
1) Warmup (Y/N)
2) Fire (Y/N)
3) Auto Oi Fault (Y/N)
4) Dim Detect Fault (Y/N)
5) Detect Disable Flt (Y/N)
6) Snsr Hdwr Fault (Y/N)
7) HIB Hdwr Fault (Y/N)
8) Int Comm Fault
9) Incompatible Flt
10) Voltage Fault (Y/N)
11) Hardware Menu
12) Oi Menu