Appendix b, Csa approval – Det-Tronics X5200 UVIR Flame Detector User Manual
Page 29
27
95-8546
13.1
aPPENDIX b
CsA AppROVAL
pRODuCTs
CLAss 4818 04 -
SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5);
Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3);
Class III; Enclosure NEMA/Type 4X;
Ultraviolet Infrared Flame Detector/Controller X5200 series, rated 18-30 Vdc, 2.8 Watts to 17.5 Watts.
Relay contacts rated 5 Amps @ 30 Vdc.
AppLICAbLE REQuIREMENTs
CSA Std C22.2 No. 25-1966
– Enclosures for use in Class II Groups E, F & G Hazardous Locations.
CSA Std C22.2 No. 30-M1986
– Explosion-Proof Enclosures for Use in Class I Hazardous Locations.
CAN/CSA C22.2 No. 94-M91
– Special Purpose Enclosures.
CSA Std C22.2 No. 142-M1987 – Process Control Equipment.
CSA Std C22.2 No. 213-M1987
– Nonincendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations.
The following accessories are CSA approved for use with the X5200 Flame Detector:
part Number
Description
102740-002
Magnet
007739-001
Magnet and Extension Pole
007290-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001
Q9033 Collar Attachment