14

13.1

sETTINg DEVICE NETWORk ADDREssEs
(EQ and EQp Models Only)
Overview of Network Addresses
Each device on the LON must be assigned a unique

address. Addresses 1 to 4 are reserved for the

controller. Valid addresses for field devices are from

5 to 250.

Important

If the address is set to zero or an address above
250, the switch setting will be ignored.

Duplicated addresses are not automatically detected.

Modules given the same address will use the number

given and report to the controller using that address.

The status word will show the latest update, which

could be from any of the reporting modules using that

address.

setting Field Device Addresses
Selection of the node address is done by setting rocker

switches on an 8 switch “DIP Switch Assembly” within

the detector’s housing. Refer to Figure 16 for switch

location.

WarnIng

The network address switches are located within
the detector housing. Disassembly of the detector
head that contains powered electrical circuits is
required to gain access to the network address
switches. For hazardous areas, the area must be
de-classified before attempting disassembly of the
device. Always observe precautions for handling
electrostatic sensitive devices.

The address number is binary encoded with each switch

having a specific binary value with switch 1 being the

LSB (Least Significant Bit), see Figure 17. The device’s

LON address is equal to the added value of all closed

rocker switches. All “Open” switches are ignored.

Example

: for node No. 5, close rocker switches 1 and

3 (binary values 1 + 4); for node No. 25, close rocker

switches 1, 4 and 5 (binary values 1 + 8 + 16).

NOTE

The field device sets the LON address only when
power is applied to the device. Therefore, it is
important to set the switches

before applying

power. If an address is ever changed, system
power must be cycled before the new address will
take effect.

After setting address switches, record the address

number and device type.

ADDRESS SWITCHES

SENSOR MODULE
REMOVED FROM HOUSING

A2191

figure 16—Location of address Switches

1

2

3

4

5

6

7

8

1

2

4

8 16 32 64 128

ON

NODE ADDRESS EQUALS THE ADDED VALUE

OF ALL CLOSED ROCKER SWITCHES

A2190

BINARY

VALUE

CLOSED = ON

OPEN = OFF

figure 17—address Switches for X5200