beautypg.com

Det-Tronics X5200 UVIR Flame Detector User Manual

Page 19

background image

17

95-8546

13.1

pERIODIC CHECkOuT pROCEDuRE
In compliance with SIL 2, a checkout of the system

using the Mag

oi

or Man

oi

feature should performed

regularly to ensure that the system is operating properly.

Refer to Table 1 in the X5200 Safety manual (95-8672) for

frequency of proof tests. To test the system, perform the

“Fire Alarm Test” as described in the “Startup Procedure”

section of this manual.

CLOCk bATTERy
The real time clock has a backup battery that will

operate the clock with no external power. Return the

device to the factory for battery replacement if needed.

NOTE

If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.

fEaTuRES

• Responds to a fire in the presence of modulated

blackbody radiation (i.e. heaters, ovens, turbines)

without false alarm.

• High speed capability.
• Built-in data logging / event monitoring, up to 1500

events (up to 1000 general, 500 alarms).

• Microprocessor controlled heated optics for

increased resistance to moisture and ice.

• Automatic, manual or magnetic

oi

testing.

• Easily replaceable

oi

plate.

• Fire, fault and auxiliary relays standard.
• 0 to 20 mA isolated output (optional).
• Eagle Quantum Premier LON/SLC output (optional).
• HART communication (optional)
• FDT/DTM capable
• A tri-color LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm

or fault conditions.

• Operates under adverse weather conditions.
• Mounting arm allows easy sighting.
• Integral wiring compartment for ease of installation.
• Explosion-proof/flame-proof detector housing. Meets

FM, CSA, ATEX and CE certification requirements.

• Class A wiring per NFPA-72.
• Meets NFPA-33 response requirement for under

0.5 second (available when model selected).

• 3 year warranty.
• Advanced signal processing (ARC/TDSA).
• RFI and EMC Directive compliant.

Associated Manuals
List of X5200 related manuals:

TITLE

FORM NuMbER

Pulse

95-8547

EQP

95-8533

SIL 2 (Safety)

95-8672

HART Addendum

95-8636

Q9033 Mounting Arm

and Collar Attachment

95-8686

Inspector Monitor Software for

X-Series Flame Detectors

95-8581