beautypg.com

Det-Tronics X9800 IR Flame Detector User Manual

Page 27

background image

25

95-8554

11.1

NOTE

Operational performance verified from –40°C to +75°C.

NOTE

An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.

NOTE

Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be
certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof
enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the
degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable
blanking elements.

NOTE

For ATEX installations, the X9800 detector housing must be electrically connected to earth ground.

The following accessories are ATEX approved for use with the X9800 Flame Detector:

part Number

Description

007290-001

Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors

007290-002

Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only

011385-001

Q9033 Collar Attachment