Det-Tronics X9800 IR Flame Detector User Manual
Page 24
95-8554
22
11.1
FM Approval and performance Report – Continued
FIELD OF VIEW
Very High sensitivity, Quick Fire Off
Fuel
size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)*
Vertical
(degrees)
Typical Vert. Response
Time (seconds)*
n-Heptane
1 x 1 foot
42.5
(13)
+45
–45
12
14
+45
–30
10
16
Methane
32 inch plume
30
(9.1)
+45
–45
7
4
+45
–30
6
4
High sensitivity, TDsA On, Quick Fire Off
Fuel
size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)*
Vertical
(degrees)
Typical Vert. Response
Time (seconds)*
n-Heptane
1 x 1 foot
25
(7.6)
+45
–45
7
7
+45
–30
6
5
Methane
32 inch plume
17.5
(5.3)
+45
–45
6
3
+45
–30
4
4
High sensitivity, TDsA On, Quick Fire On
Fuel
size
Distance
feet (m)
Horizontal
(degrees)
Typical Horiz. Response
Time (seconds)*
Vertical
(degrees)
Typical Vert. Response
Time (seconds)*
Black
Powder
40 Grams
5
(1.5)
+45
–45
0.04
0.03
+45
–30
0.04
0.04
*Add 2 seconds for EQP model.
FALsE ALARM IMMuNITy
High sensitivity, TDsA On, Quick Fire Off
False Alarm souce
Distance feet
(m)
Modulated Response
unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
NA
No alarm
No alarm
Arc welding
15 (4.6)
No alarm
No alarm
70 w sodium vapor lamp
3 (0.9)
No alarm
No alarm
250 w mercury vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
10 (3)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
*Add 2 seconds for EQP model.