startup proceDure
When installation of the equipment is complete, perform
the “Fire Alarm Test” below.
FIRE ALARM TEsT
1. Disable any extinguishing equipment that is
connected to the system.
2. Apply input power to the system.
3. Initiate an oi test. (See “Magnetic oi / Manual oi”
under Optical Integrity in the Description section of
this manual.
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting”
section.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (Det-Tronics'
Q1201C Laser Aimer is recommended for this
purpose.)
6. Enable extinguishing equipment when the test is
complete.
troubleshooting
WarnIng
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.
1. Disable any extinguishing equipment that is
connected to the unit.
2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning
of the detector viewing windows.)
3. Check input power to the unit.
4. If the fire system has a logging function, check the
fire panel log for output status information. See Table
3 for information regarding 0 to 20 mA output.
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.
6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check for
high levels of background IR radiation by covering
the detector with the factory supplied cover or
aluminum foil. If the fault condition clears, extreme
background IR radiation is present. Re-adjust the
view of the detector away from the IR source or
relocate the detector.
If none of these actions corrects the problem, return the
detector to the factory for repair.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
maintenance
Important
Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
WarnIng
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.
table 3—current Level output troubleshooting guide
1If fault continues, return device to factory for repair.
2See “Maintenance” section for cleaning procedure.
Current Level
(±0.3 mA)
status
Action
0 mA
Power Fault
Check system wiring.
1 mA
General Fault
Cycle power.
1
2 mA
oi Fault
Clean windows.
2
4 mA
Normal Operation
16 mA
Hi Background IR
Fault
Remove IR source or
aim detector away
from IR source.
20 mA
Fire Alarm