Hart activity indicator, Transmitter front panel menu inputs, Universal command revision – CiDRA SONARtrac Quick Start User Manual
Page 23: Polling address, Hart activity indicator -3, Transmitter front panel menu inputs -3, Figure 7, Transmitter indicator of hart activity -3, Figure 8, Hart universal command revision -3

4.2.4
HART Activity Indicator
When the SONARtrac receives a valid HART message, an indicator
will appear on the lower right of the SONARtrac display. This indicator
will be removed if another message is not rec
eived in 10 seconds.
V
F
235 gal/min
T
O
T
19345 gal
SONARTRAC VF
H/
Figure 7
Transmitter Indicator of HART Activity
4.2.5
Transmitter Front Panel Menu Inputs
The following HART options are available from the transmitter front
panel.
4.2.5.1
Universal Command Revision
The most generally deployed HART Revision is 5, the SONARtrac
default HART Protocol Revision. In the case where the SONARtrac
transmitter must communicate with a Revision 6 HART Master, this
option may be changed to 6.
Figure 8
HART Universal Command Revision
4.2.5.2 Polling
Address
When using a Point to Point topology, leave the Polling Address at 0.
If using Multi-Drop, set the Polling Address to a number unique from
any other HART devices on the Multi-Drop loop.
Figure 9
HART Polling Address
Copyright © 2007 CiDRA Corporation
Page 4-3
20984-01 Rev 01