NOTE: Stilling pipes are an excellent solution for liquid level

applications where an unobstructed path to the target is not feasible

(see stilling pipe mounting on page 9 for details).

• When mounting outdoors, it’s best to shade the sensor from direct

sunlight. Direct sunlight can warm the sensor housing above the ambient

temperature causing false temperature readings and overcompensation by

the sensor.

• Installation

Proper sensor mounting is critical for successful operation of an ultrasonic

sensor. Using the following guidelines can help ensure trouble free installation

and operation:

• Ensure that the sensor face is perpendicular to the target surface. If the

target is more than a few degrees off perpendicular, it may not be

detected. Targets at greater distances will require more precise sensor

alignment.

• Mount the sensor in a location that provides an unobstructed column

of air from the sensor to the target. The required width of the air

column depends on several factors, including the angle and reflective

characteristics of any potential targets on the edge of the column, the

sensitivity setting of the sensor, the maximum distance to the target, and

the reflective characteristics of the target itself. Generally speaking a 3 to 4

foot diameter unobstructed column is sufficient even at longer ranges.

11.4 in.

19 in. 22.8 in. 26.6 in. 30.4 in. 34.2 in. 38 in.

3.8 in. 7.6 in.

15.2 in.

2 ft.

4 ft.

3 ft.

5 ft.

6 ft.

7 ft.

8 ft.

9 ft.

10 ft.

1 ft.

Typical beam spread of a sensor operating at maximum sensitivity