• Wiring

Always use shielded cable. It is recommended that twisted-pair cable be used
between sensors when connec! ng mul! ple sensors to the Modbus network.

NOTE:

Always use a high quality power supply that will deliver clean, stable

voltage.

The MNU series sensors are wired in a daisy-chain confi gura! on, as shown
below. Each sensor should be connected individually and assigned a unique
address before wiring the sensor into the Modbus network.

Power
Supply

Master
Device

RS-485 A

RS-485 B

Vdc

Vdc

+

-

Sensor 1

V+ V-

A

B

Sensor 2

V+ V-

A

B

Sensor 3

V+ V-

A

B

Use Shielded Cable

120 Ohm
Terminating
Resistor

120 Ohm
Terminating
Resistor

Modbus Daisy-Chain Wiring

Mirco Connector:
Pin 1 (Brown)

+24 VDC

Pin 2 (White)

RS-485 A

Pin 3 (Blue)

DC Common

Pin 4 (Black)

RS-485 B

4-Conductor Cable:
Red

+24 VDC

Black

DC Common

White

RS-485 A

Green

RS-485 B