MNU Series Ultrasonic Sensors

7

Automa! on Products Group, Inc.

APG...Providing tailored solu• ons for measurement applica• ons

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

• Always mount above the highest an! cipated target level by at least the

published minimum blanking distance. If a target enters into the blanking
area, error in the detec! on will occur. It is always advisable to allow for
suffi

cient headroom to ensure that the target does not enter the blanking

area.

• Generally it is advisable to mount the sensor away from any vessel fi ll

spouts. However, if heavy foam is expected, it is o$ en helpful to mount the
Sensor near a fi ll spout where the foam is being dispersed.

• Avoid moun! ng the sensor in the direct center of a tank with a signifi cantly

domed top. A domed top can act as parabolic dish, amplifying small
undesired signals that may be present inside the tank.

• Avoid moun! ng the sensor in close proximity to tank walls, especially on

tanks with corrugated walls or in applica! ons where product buildup on
the tank walls may occur.