MNU Series Ultrasonic Sensors

Rev. B1, 5/13

18

Automa! on Products Group, Inc.

APG...Providing tailored solu• ons for measurement applica• ons

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

• Parameter Descrip! ons

Device Address

(1 to 255) (40400)

Each device within the Modbus network must be assigned a unique address.
Each MNU sensor should be connected to the network individually and as-
signed an address. By default the each sensor is set to address 1.

Units

(1 to 3) (40401)

Determines the unit of measure for the Calculated Reading (input registers

30303-30304) when in Applica! on Types 1, 2 or 7 (see below).

Applica! on Type

(0 to 11) (40402)

Determines how the sensor calculates the readings.

Applica! on Type 0: Distance to target

(measurement result in register 30300)

Register

Func! on

Value Range

40401

Units

1 to 3

40402

Applica! on Type

0

40404

Decimal Place

0 to 3

40405

Max Distance

0 to 10364 mm

Applica! on Type 1: Depth of level

(measurement result in register 30300)

Register

Func! on

Value Range

40401

Units

1 to 3

40402

Applica! on Type

1

40404

Decimal Place

0 to 3

40405

Max Distance

≥ Empty Distance

40406

Full Distance

Typically = Blanking Distance

40407

Empty Distance

0 to 10364 mm

Distance

Level