beautypg.com

APG MNU Slave Sensor user manual User Manual

Page 33

background image

Rev. B1, 5/13

MNU Series Ultrasonic Sensors

33

Automa! on Products Group, Inc.

APG...Providing tailored solu• ons for measurement applica• ons

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

•Web Alarming (40430 to 40435)

When the MNU is interfaced with an LOE or RST-5002 web-enabled master
device, it can be confi gured to generate website alarms via levelandfl ow.com
(refer to the LOE or RST-5002 user manual for more informa# on about website
alarms and using levelandfl ow.com).

Trip Alarm 1 (40430) or Alarm 2 (40433) Distance

Sets the level (in mm), beginning the bo$ om of the stem, to the fi rst (lowest)
actua# on point (refer to next page for more informa# on).

Trip Alarm 1 Window (40431 or 40434)

Sets the level (in mm), beginning from the Trip Distance loca# on, to the second-
ary actua# on point (refer to next page for more informa# on).

Trip Alarm 1 Type (40432 or 40435)

Determines the opera# onal logic performed by the Trip Alarm (refer to chart on
next page for more informa# on).

Confi guring Trip Alarm Types for Website Alarming:

(refer to Trip Types chart on next page)

Placing a “1” in front of any of the Trip Types designates an ac# ve trip point as
an alarm condi# on. For example; Trip Type 3 would be designated as 13, and
would ini# ate a website alarm whenever the trip is ac# ve (on).

Placing a “2” in front of any of the Trip Types designates an inac# ve trip point as
an alarm condi# on. For Example; Trip Type 3 would be designated as 23, and
would ini# ate a website alarm whenever the trip is inac# ve (off ).

This manual is related to the following products: