Check, test & start procedure, Warning – Aerovent IM-121 User Manual
Page 6
6
Aerovent IM-121
Table 2. Wheel to Inlet Venturi
MODEL
GAP
OVERLAP
ACX 070/075
---
0.25
ACX*
---
0.50
ATB/ATBR/AWX/AWXR
0.06
---
ACXD
0.25
---
ATD/ATDR/ATDW/ATDWR
0.06
---
*all sizes except 070 and 075.
Check, Test & Start Procedure
WARNING
Electric shock hazard. Could cause severe injury or
death. Failure to bond the frame of this equipment
to the building electrical ground by use of the
grounding terminal provided or other acceptable
means may result in electrical shock. Disconnect
electric power before servicing equipment. Service
to be performed only by qualified personnel.
BEFORE START-UP: Disconnect power to this unit
before servicing the unit.
1. Check to verify that the wheel is free to rotate.
2. For optimum fan performance make sure that the
wheel to inlet venturi gap or overlap is maintainted.
See Table 2.
3. Verify that supply voltage on the line side of discon-
nect agrees with voltage on fan data plate and is
within the 10% utilization voltage.
4. Apply power to unit and check rotation of wheel with
the directional arrow on the unit. See Table 1.
WARNING: Rotation is critical. If allowed to operate
in the wrong direction, the motor will overload and
burn out.
WARNING: Especially check three-phase units for
rotation. For three-phase, rotation can be changed by
interchanging any two of the three line leads. If unit is
checked on temporary wiring, it should be rechecked
when permanently installed. Motor burn-out or tripped
overload protection devices are usually the result of
wrong rotation.
5.
Electrical Input Check: Perform check of fan ampere
draw and verify that motor nameplate amps are not
exceeded. Take into account the service factor range
if motor is nameplated above a 1.0 service factor.
6. Fan RPM should be checked and verified with a
tachometer.
7.
Units with Speed Control (Direct Drive): Verify that
speed controller gives desired operating range of
RPM. If minimum speed value is not desired, it may
be adjusted. See page 7.
NOTE: The fan should not need balancing, as it was
balanced at the factory to be within stringent vibration
levels before shipment. However, there are several
things that may cause vibration, such as rough han-
dling in shipment and installation, weak foundations
and alignments.
Table 1. Wheel Rotation*
MODEL
CW
CCW
ACX
all other
070, 075
ATB/ATBR/AWX/AWXR
all other
160, 180
ACXD
---
all
ATD/ATDR/ATDW/ATDWR
---
all
* Wheel rotation is determined when viewed from top of fan
(opposite air intake).
Note: On fans with three phase motors the wheel rotation can
be changed by reversing any two power leads.
Figure 1. Fan Wheel Rotation - View from Exhaust End
WHE
EL ROTATIO
N
CURB
BASE
FAN
WHEEL
HOUSING
Note: CCW rotation shown, CW rotation is similar but opposite.