beautypg.com

Roof fan installation wall fan installation, Electrical connection – Aerovent IM-121 User Manual

Page 5

background image

Aerovent IM-121

5

Roof Fan Installation

Wall Fan Installation

1. Your wall fan is shipped with a wall mounting brack-

et. Refer to the wall fan dimensional drawing on

page 4 for mounting hole locations. Consideration

should be taken when choosing wall fan location

with regard to other buildings, parking lots, etc.

2. After drilling pilot holes, bolt the wall mounting

bracket to the wall through the holes provided on

the bracket flange using eight (8) lag bolts.

3. Position fan with the motor compartment breather

tube facing downward.

4. Run wires through conduit to switch. Leave some

slack in the wire in the motor compartment so that

the motor and wheel assembly can be lifted for

inspection and cleaning. If fan has an external dis-

connect switch (standard on restaurant units) bring

power to switch.

5. Bolt the fan base to the wall bracket using hardware

provided.

6. Make connection to the disconnect switch per

above electrical instructions.

7. Restaurant fan installation must be in compliance

with local codes and the National Fire Protection

Association’s NFPA-96.

8. Models ACXD, ATD, ATDR, ACX, ATB and ATBR are

not designed to be mounted to a wall.

Electrical Connection

1. Connect supply wiring to the disconnect switch

(non-fused standard). Check the wiring diagrams on

the motor for connections.

2. The motor is factory set at the voltage marked on

the fan nameplate. Check the line voltage with the

nameplate voltage and wiring diagrams.

3. The main power wiring should be sized for the

ampacity shown on the dataplate. Size wires in

accordance with the ampacity tables in Article 310

of the National Electrical Code. If long wires are

required, it may be necessary to increase wire size

to prevent excessive voltage drop. Wires should be

sized for a maximum of 3% voltage drop.

CAUTION: Use copper conductors only.

CAUTION: Protect wiring from sharp edges. Leave

some slack in the line to prevent damage.

4. Disconnect switches are not fused. The power leads

must be protected at the point of distribution in

accordance with the fan dataplate.

5. On fans without a thermal protector integral to the

motor (refer to unit or motor dataplate to determine

if protector is present) a separate overload device

is required. Refer to Sections 430-32 of the N.E.C.

for sizing.

6. All units must be electrically grounded in accordance

with local codes or, in the absence of local codes,

with the latest edition of the National Electrical

Code (ANSI/NFPA 70). A ground lug is provided as

standard in the unit terminal box. Size grounding

conductor in accordance with Table 250-95 of the

National Electrical Code.

DO NOT use the ground

lug for connecting a neutral conductor.

7. Supply voltage to the power ventilator should not

vary by more than 10% of the value indicated

on the unit dataplate. Phase unbalance must not

exceed 2%.

WARNING: Failure of motor due to operation on

improper line voltage or with excessive phase unbal-

ance constitutes product abuse and may cause

severe damage to the unit’s electrical components.

Downblast Fans:
1. Position the fan with its wiring conduit in line with

the wiring coming up through the roof curb and

damper (if present). If the fan has an external dis-

connect switch, position the fan with the junction

box towards the power supply.

Upblast Fans:
1. Position the fan with its wiring conduit, coming

through the outer fan housing or its external discon-

nect, towards the power supply.

2. Run wires through the conduit to the switch. Leave

some slack in the wire in the motor compartment

so the motor and wheel assembly can be lifted for

inspection and cleaning.

3. Bolt the fan base to the roof curb through the holes

provided on the base using eight (8) lag bolts.

4. Make connection to the disconnect switch per

above electrical instructions.

5. Restaurant fan installation must be in compliance

with local codes and the National Fire Protection

Association’s NFPA-96.