Intelli-Tank Manual (106759)071006

– 16 –

Class 1




Condition

Evaluate

The bottom two

LEDs are on and

occasionally they go

out and the top two

flash and then return

to the bottom two

LEDs on (or vice-

versa). (REMOTE).

Check for large noise spikes on the data line.
Insure that the unit’s ground potential is the same as the Master’s.
Insure that the data line is not chaffed and making contact with

other electrical wires.

The points calibrated

seemed to have

changed.

Self test the unit to check for any malfunctions.
Check the pressure transducer for problems.
Recalibrate the unit and take a voltage reading from the transducer

(pin 7 on the unit’s connector) at each calibration point. When the

calibration points again look wrong check the voltages at those

points and determine if they are the same as the voltage reading

taken during calibration.

Unit will not dim

display.

Insure the Dim input voltage on Pin 3 is at least 9V. Recalibrate dim

setting (RLLR LLLR). If unit does not dim LEDs while in dim

calibrate mode, replace unit.

The two top amber

LEDs are flashing

together.

A calibration was started on the unit but not completed correctly.

Set the unit to a REMOTE unit (LRLR LRLR) or calibrate it as a

MASTER (follow calibration steps exactly).

Top LED is the only

LED illuminated.

The unit has had a memory error.
Attempt to set the unit back to REMOTE or MASTER as required.