Class1 106759 - ITL 4LT with 1-wire COM 106296 106299 User Manual
Page 10
Intelli-Tank Manual (106759)071006
– 10 –
Class 1
The Intelli-Tank display can be calibrated four different ways: 1-point and 2-point
(level calibration), 5-point and 9-point (volume calibration).
To enter calibration mode use a magnet and activate the magnetic switches in
the order of the appropriate password.
The display has two magnetic switches (left and right). The magnetic switches are activated by using a
magnet and touching the front of the display on either side of LED 2.
For best results the magnet should be positioned over the desired magnet approximately 2 inches from the
front of the display, pushed directly to the front of the display, and then pulled back to the start position.
The LEDs on the display will indicate which switch was activated (upper two LEDs = left switch, bottom
LED = right switch) for approximately half a second and then the display will go blank.
The maximum time between magnetic switch activations is two seconds. If longer than two seconds have
passed between activations the unit will resume normal operation and the password attempted will be reset.
Entering an invalid password will initiate a “wave off” pattern on the
display. (Two center LEDs, two outer LEDs flashing quickly for 8
cycles.) The unit will then resume its normal operation and the user can
attempt to re-enter the password.
Calibrate the unit by entering the desired point calibration –
1 point
RLLR LRRL
2 point
RLLR LLRL
5 point
RLLR LRLR
9 point
RLLR RLLR