beautypg.com

Emi-automatic, Riming, Alve – Hale SPV User Manual

Page 8

background image

S

emi-Automatic

P

riming

V

alve

6

Retrofit Installation:

When installing the Hale SPV as a retrofit on
a midship fire pump the following
procedures shall be followed. (Refer to
figure 5)

1. Place the apparatus out of service in

accordance with departmental
procedures. Drain all water from pump
b o d y .

WARNING: Disconnect or turn-off master
battery switch prior to service of the
Hale SPV electrical components. Make
sure there is no power at the primer
solenoid before starting service
procedures.

2. Open the pump operator panel and

gain access to the existing Hale PVG.

3. Disconnect the electrical leads and

vacuum hoses to the Hale PVG.

4. If the Hale PVG is mounted at the

operator panel, remove the Hale PVG
and placard.

5. Install the panel placard and

momentary contact push-button
provided with the Hale SPV on the
operator panel.

NOTE: A spacer is required where the
Hale PVG was removed to allow
mounting of the push-button switch.
Manufacture a spacer using the
template in figure 4 as a guide. The
outer surface of the spacer must be flat
to allow proper installation of the panel
placard push-button switch. Use
material thickness and fastening devices
that leave a flat surface.

6. Connect electrical leads to the

momentary contact push-button.

7. Locate the priming valve flange on the

midship pump. (Refer to figure 5) The
priming valve flange is located next to
the gearbox on the midship pump.

8. Remove the

7

/

16

-14 x 1-

1

/

4

inch long cap

screws that hold the priming flange,
hose and fittings on the midship pump
body. Remove the flange assembly
from the pump body.

9. Remove the strainer and seal ring from

the pump body. Clean the strainer of all
debris. DO NOT discard the strainer as it
must be used with the Hale SPV.

10. Apply a light coat of thread locking

compound (Loctite #290 or equal) to

Figure 4. Panel Placard Spacer

0.64 IN. (16 mm)

THRU HOLE

2.32 IN.

(59 mm)

1.16 IN.

(29 mm)

0.25 IN. (6 mm)

RAD TYP

(2) THRU HOLES FOR

SPACER FASTENERS

2.44 IN. (62 mm)

1.22 IN. (31 mm)

1 IN. (25 mm)

NOTE: MATERIAL THICKNESS AND SPACER
FASTENERS MUST ALLOW FOR A FLAT SURFACE
WHEN THIS SPACER IS MOUNTED ON THE
OPERATOR PANEL. USE COUNTERSUNK
FLATHEAD SCREWS OR PEM TYPE FASTENERS