Bryant 580D User Manual
Page 8

PHYSICAL DATA — 580D036-072
UNIT SIZE 580D
036
048
060
072
NOMINAL CAPACITY (tons)
3
4
5
6
OPERATING WEIGHT (lb)
Unit
Al/Al*
460
470
490
565
Al/Cu*
465
476
497
576
Cu/Cu*
468
482
505
587
Economizer
Durablade
34
34
34
34
Parablade
42
42
42
42
Roof Curb†
115
115
115
115
COMPRESSOR
Hermetic
Quantity
1
1
1
1
No. Cylinders (per Circuit)
2
2
2
2
Oil (oz)
50
50
50
54
REFRIGERANT TYPE
R-22
Expansion Device
Acutrol™ Feed Device
Operating Charge (lb-oz)
Circuit 1
3-6
4-11
5-13
7-8
Circuit 2
—
—
—
—
CONDENSER COIL
Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in.
1...17
1...17
1...17
2...17
Total Face Area (sq ft)
7.36
11.39
13.19
10.42
CONDENSER FAN
Propeller Type
Nominal Cfm
3500
4000
4000
4000
Quantity...Diameter (in.)
1...22.0
1...22.0
1...22.0
1...22.0
Motor Hp...Rpm
1
⁄
4
...1100
1
⁄
4
...1100
1
⁄
4
...1100
1
⁄
4
...1100
Watts Input (Total)
325
325
325
325
EVAPORATOR COIL
Enhanced Copper Tubes, Aluminum Double-Wavy Fins
Rows...Fins/in.
2...15
2...15
3...15
4...15
Total Face Area (sq ft)
4.17
5.5
5.5
5.5
EVAPORATOR FAN
Centrifugal Type
Quantity...Size (in.)
Std
1...10 x 10
1...10 x 10
1...11 x 10
1...10 x 10
Alt
1...10 x 10
1...10 x 10
1...10 x 10
—
Type Drive
Std
Direct
Direct
Direct
Belt
Alt
Belt
Belt
Belt
—
Nominal Cfm
1200
1600
2000
2400
Motor Hp
Std
—
—
—
—
Alt
—
—
—
—
Maximum Continuous Bhp
Std
.34
.75
1.20
2.40
Alt
1.00
1.00
1.80
—
Motor Frame Size
Std
48
48
48
56
Alt
48
48
48
—
Nominal Rpm High/Low
Std
860/800
1075/970
1075/970
—
Alt
—
—
—
—
Fan Rpm Range
Std
—
—
—
1070-1460
Alt
760-1000
835-1185
900-1300
—
Motor Bearing Type
Ball
Ball
Ball
Ball
Maximum Allowable Rpm
2100
2100
2100
2100
Motor Pulley Pitch Diameter Min/Max (in.)
Std
—
—
—
2.8/3.8
Alt
1.9/2.9
1.9/2.9
2.4/3.4
—
Nominal Motor Shaft Diameter (in.)
Std
1
⁄
2
1
⁄
2
1
⁄
2
5
⁄
8
Alt
1
⁄
2
1
⁄
2
1
⁄
2
—
Fan Pulley Pitch Diameter (in.)
Std
—
—
—
4.5
Alt
4.5
4.0
4.5
—
Nominal Fan Shaft Diameter (in.)
—
—
—
—
Belt, Quantity...Type...Length (in.)
Std
—
—
—
1...A...40
Alt
1...A...34
1...A...34
1...A...39
—
Pulley Center Line Distance (in.)
Std
—
—
—
14.7-15.5
Alt
10.0-12.4
10.0-12.4
14.7-15.5
—
Speed Change per Full Turn of
Std
—
—
—
80
Movable Pulley Flange (rpm)
Alt
48
70
80
—
Movable Pulley Maximum Full Turns
Std
—
—
—
5
From Closed Position
Alt
5
5
5
—
Factory Setting
Std
—
—
—
3
Alt
3
3
3
—
Factory Speed Setting (rpm)
Std
—
—
—
1225
Alt
856
975
1060
—
Fan Shaft Diameter at Pulley (in.)
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
LEGEND
Al
— Aluminum
Bhp — Brake Horsepower
Cu
— Copper
*Evaporator coil fin material/condenser coil fin material. Contact your
local representative for details about coated fins.
†Weight of 14-in. roof curb.
**Rollout switch lockout is manually reset by interrupting power to unit
or resetting thermostat.
††Requires an optional or accessory Controls Upgrade Kit.
NOTE: The 580D036-150 units have a loss-of-charge/low-pressure
switch (accessory or option) located in the liquid line.
8