PERFORMANCE DATA (cont)
EVAPORATOR-FAN MOTOR PERFORMANCE
UNIT
EVAPORATOR-FAN
MOTOR
UNIT
VOLTAGE
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
MAXIMUM
AMP DRAW
580D036
Standard
208/230
0.34
440
2.9
460
1.4
575
1.4
Alternate
208/230
1.00
1000
5.4
460
2.3
575
2.3
580D048
Standard
208/230
0.75
850
3.5
460
1.8
575
1.8
Alternate
208/230
1.00
1000
5.4
460
2.3
575
2.3
580D060
Standard
208/230
1.20
1340
5.9
460
3.2
575
3.2
Alternate
208/230
1.80
1921
8.9
460
4.7
575
4.7
580D072
Standard
208/230
2.40
2120
6.1
460
2.7
575
2.7
580D090
Standard
208/230
2.40
2120
6.1
460
2.7
575
2.7
580D102
Standard
208/230
2.40
2120
6.1
460
2.7
575
2.7
580D120
Standard
208/230
2.40
2120
6.1
460
2.7
575
2.7
Alternate
208/230
2.90
2615
7.9
460
3.6
575
3.6
580D150
Standard
208/230
4.20
3775
11.1
460
5.0
575
5.0
Alternate
208/230
5.25
4400
15.0
460
7.4
575
7.4
579F180
Standard
208/230
4.25
3775
10.5
460
4.8
579F216
Standard
208/230
5.90
5180
15.8
460
7.9
579F240
Standard
208/230
8.70
7915
22.0
460
9.50
8640
13.0
579F300
Standard
208/230
10.20
9510
28.0
460
11.80
11,000
14.6
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
55