PERFORMANCE DATA (cont)
FAN PERFORMANCE — 579F180-300 UNITS
579F180 (15 TONS)
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
801
1.05
933
890
1.26
1119
971
1.46
1297
1050
1.67
1483
1125
1.88
1670
1200
2.12
1883
4800
843
1.25
1110
928
1.47
1306
1006
1.68
1492
1081
1.90
1687
1153
2.13
1892
1223
2.36
2096
5100
885
1.47
1306
968
1.70
1510
1043
1.93
1714
1114
2.16
1918
1183
2.40
2131
1250
2.64
2345
5400
927
1.71
1519
1008
1.95
1732
1080
2.20
1954
1148
2.44
2167
1214
2.69
2389
1279
2.94
2611
5700
971
1.98
1758
1049
2.24
1989
1118
2.50
2220
1134
2.75
2442
1247
3.01
2673
1309
3.28
2913
6000
1016
2.28
2025
1091
2.55
2265
1158
2.83
2513
1222
3.10
2753
1282
3.36
2984
1342
3.64
3233
6300
1059
2.60
2309
1133
2.89
2567
1198
3.17
2815
1259
3.46
3073
1318
3.74
3321
1375
4.02
3570
6600
1104
2.96
2629
1174
3.26
2895
1239
3.56
3162
1297
3.86
3428
1355
4.15
3686
1405
4.40
3970
6900
1150
3.35
2975
1218
3.67
3259
1281
3.98
3535
1340
4.20
3730
1392
4.55
4040
1460
4.95
4350
7200
1194
3.77
3348
1260
4.10
3641
1325
4.40
3907
1390
4.65
4130
1440
5.10
4530
1510
5.30
4700
7500
1238
4.23
3758
1300
4.50
3996
1370
4.90
4351
1435
5.00
4440
1490
5.60
4970
—
—
—
579F180 (15 TONS)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
1275
2.39
2123
1349
2.70
2398
1421
3.03
2691
1490
3.39
3011
4800
1293
2.62
2327
1364
2.92
2593
1433
3.24
2877
1501
3.59
3188
5100
1316
2.90
2575
1382
3.18
2824
1448
3.49
3099
1514
3.86
3428
5400
1342
3.20
2842
1403
3.47
3082
1466
3.77
3348
1529
4.16
3694
5700
1370
3.54
3144
1429
3.81
3384
1487
4.11
3650
—
—
—
6000
1401
3.92
3481
1458
4.20
3730
1525
4.50
3776
—
—
—
6300
1430
4.30
3820
1490
4.55
4040
—
—
—
—
—
—
6600
1461
4.85
4305
1530
5.00
4440
—
—
—
—
—
—
6900
1500
5.35
4750
—
—
—
—
—
—
—
—
—
7200
—
—
—
—
—
—
—
—
—
—
—
—
7500
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory Installed Option
Watts — Input Watts to Motor
*Standard low-medium static drive range is 891 to 1179 rpm. Alternate
high static drive range is 1227 to 1550 rpm. Other rpms require a field-
supplied drive.
NOTES:
1. Static pressure losses (i.e., economizer) must be added to exter-
nal static pressure before entering Fan Performance table. See
Accessory/FIOP Static Pressure table on page 52 for more
information.
2. Interpolation is permissible. Do not extrapolate.
3. Maximum continuous bhp is 4.25 and the maximum continuous
watts are 3775. Extensive motor and drive testing on these units en-
sures that the full horsepower range of the motor can be utilized with
confidence. Using your fan motors up to the watts rating shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.
47