Bryant 580D User Manual
Page 20

BASE UNIT DIMENSIONS — 579F240,300
UNIT
579F
CORNER WEIGHT*
DIMENSION
X
A
B
C
D
lb
kg
lb
kg
lb
kg
lb
kg
ft-in.
mm
240
520 235 508 230 532 241 640 290
3-2
965
300
527 239 545 247 578 262 600 272
3-7
1092
*Weights are for unit only (aluminum plate fins) and do not include op-
tions or crating.
NOTES:
1. Dimensions in (
) are in millimeters.
2.
Center of gravity.
3.
Direction of airflow.
4. Ductwork to be attached to accessory roof curb or
adapter only.
5. Minimum clearance:
a. Rear: 7
Ј
0
Љ
(2134) for coil removal. This dimension
can be reduced to 4
Ј
0
Љ
(1219) if conditions permit
coil removal from the top.
b. 4
Ј
0
Љ
(1219) to combustible surfaces, all four sides
(includes between units).
c. Left side: 4
Ј
0
Љ
(1219) for proper condenser coil
airflow.
d. Front: 4
Ј
0
Љ
(1219) for control box access.
e. Right side: 4
Ј
0
Љ
(1219) for proper operation of
damper and power exhaust (if so equipped).
f. Top: 6
Ј
0
Љ
(1829) to assure proper condenser fan
operation.
g. Bottom: 14
Љ
(356) to combustible surfaces (when not
using curb or adapter).
h. Control box side: 3
Ј
0
Љ
(914) to ungrounded surfaces
(non-combustible).
i. Control box side, 3
Ј
6
Љ
(1067) to block or concrete
walls, or other grounded surfaces.
j. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the condenser coil
and the damper/power exhaust as stated in Note No. 5,
a removable fence or barricade requires no clearance.
7. Dimensions are from outside of corner post. Allow
0
Ј
-
5
⁄
16
Љ
(8) on each side for top panel drip edge.
8. Do not locate adjacent units with the discharge facing
economizer inlet.