PHYSICAL DATA — 580D090-150

UNIT SIZE 580D

090

102

120

150

NOMINAL CAPACITY (tons)

7

1

2

8

1

2

10

12

1

2

OPERATING WEIGHT (lb)

Unit

Al/Al*

870

880

1035

1050

Al/Cu*

881

896

1057

1077

Cu/Cu*

893

907

1080

1100

Economizer

Durablade

44

44

44

44

Parablade

62

62

62

62

Roof Curb†

143

143

143

143

COMPRESSOR

Hermetic

Quantity

2

2

2

2

No. Cylinders (per Circuit)

2

2

2

2

Oil (oz)

50 ea

50 ea

50 ea

54 ea

REFRIGERANT TYPE

R-22

Expansion Device

Acutrol™ Feed Device

Operating Charge (lb-oz)

Circuit 1

4-13

6-14

5-13

8-10

Circuit 2

4-14

6- 3

5-14

8- 8

CONDENSER COIL

Enhanced Copper Tubes, Aluminum Lanced Fins

Rows...Fins/in.

1...17

2...17

2...17

2...17

Total Face Area (sq ft)

20.50

18.00

17.42

25.00

CONDENSER FAN

Propeller Type

Nominal Cfm

6500

6500

7000

7000

Quantity...Diameter (in.)

2...22

2...22

2...22

2...22

Motor Hp...Rpm

1

4

...1100

1

4

...1100

1

4

...1100

1

4

...1100

Watts Input (Total)

600

600

600

600

EVAPORATOR COIL

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

Rows...Fins/in.

3...15

3...15

3...15

4...15

Total Face Area (sq ft)

8.0

8.0

10.0

11.1

EVAPORATOR FAN

Centrifugal Type

Quantity...Size (in.)

Std

1...15 x 15

1...15 x 15

1...15 x 15

1...15 x 15

Alt

1...15 x 15

1...15 x 15

1...15 x 15

Type Drive

Std

Belt

Belt

Belt

Belt

Alt

Belt

Belt

Belt

Nominal Cfm

3000

3400

4000

5000

Motor Hp

Std

Alt

Maximum Continuous Bhp

Std

2.40

2.40

2.40

4.20

Alt

2.90

5.25

Motor Frame Size

Std

56

56

56

56

Alt

56

56

Nominal Rpm High/Low

Fan Rpm Range

Std

590-840

685-935

685-935

860-1080

Alt

685-935

835-1085

900-1260

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Allowable Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

2.4/3.4

2.8/3.8

2.8/3.8

4.0/5.0

Alt

2.8/3.8

3.4/4.4

3.1/4.1

Nominal Motor Shaft Diameter (in.)

Std

5

8

5

8

5

8

7

8

Alt

7

8

7

8

Fan Pulley Pitch Diameter (in.)

Std

7.0

7.0

7.0

8.0

Alt

7.0

7.0

5.9

Nominal Fan Shaft Diameter (in.)

Belt, Quantity...Type...Length (in.)

Std

1...A...49

1...A...49

1...A...49

1...A...52

Alt

1...A...49

1...A...49

1...BX...46

Pulley Center Line Distance (in.)

Std

16.75-19.25

16.75-19.25

15.85-17.50

15.85-17.50

Alt

16.75-19.25

15.85-17.50

15.85-17.50

Speed Change per Full Turn of

Std

50

50

50

44

Movable Pulley Flange (rpm)

Alt

50

50

50

Movable Pulley Maximum Full Turns

Std

5

5

5

5

From Closed Position

Alt

5

5

6

Factory Setting

Std

5

5

5

5

Alt

5

5

5

Factory Speed Setting (rpm)

Std

590

685

685

860

Alt

685

835

960

Fan Shaft Diameter at Pulley (in.)

1

1

1

1

LEGEND

Al

Aluminum

Bhp — Brake Horsepower
Cu

Copper

*Evaporator coil fin material/condenser coil fin material. Contact your

local representative for details about coated fins.

†Weight of 14-in. roof curb.

**Rollout switch lockout is manually reset by interrupting power to unit

or resetting thermostat.

††Requires an optional or accessory Controls Upgrade Kit.

NOTE: The 580D036-150 units have a loss-of-charge/low-pressure
switch (accessory or option) located in the liquid line.

10