Bryant 580D User Manual
Page 35

PERFORMANCE DATA (cont)
FAN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont)
580D090 (7
1
⁄
2
TONS)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2250
514
0.55
562
593
0.76
723
662
0.99
907
724
1.22
1097
781
1.78
1318
2300
521
0.57
577
600
0.79
747
668
1.02
932
730
1.26
1131
786
1.50
1335
2400
536
0.63
623
613
0.85
795
680
1.09
989
741
1.34
1199
796
1.59
1413
2500
551
0.69
669
626
0.93
859
693
1.17
1056
753
1.43
1275
808
1.69
1499
2550
559
0.72
692
634
0.97
891
700
1.21
1089
759
1.48
1318
814
1.74
1543
2600
567
0.75
716
641
1.00
916
706
1.25
1123
764
1.52
1353
819
1.79
1587
2700
582
0.83
779
655
1.08
981
719
1.34
1199
776
1.61
1430
831
1.89
1674
2800
598
0.90
835
670
1.17
1056
732
1.43
1275
789
1.71
1517
842
2.00
1770
2900
614
0.98
899
684
1.25
1123
745
1.53
1361
802
1.81
1604
854
2.11
1866
3000
630
1.07
973
699
1.35
1207
759
1.63
1147
815
1.92
1700
866
2.23
1971
3100
646
1.16
1047
714
1.45
1292
773
1.74
1543
828
2.04
1805
878
2.35
2076
3200
662
1.26
1131
729
1.55
1378
787
1.86
1648
841
2.16
1910
891
2.48
2188
3300
679
1.36
1216
744
1.66
1473
801
1.98
1753
854
2.29
2023
904
2.61
2300
3400
695
1.47
1310
759
1.78
1578
816
2.10
1858
867
2.42
2136
917
2.75
2420
3500
712
1.59
1413
774
1.90
1683
830
2.23
1971
881
2.56
2257
930
2.90
2546
3600
729
1.71
1517
790
2.03
1796
845
2.37
2093
895
2.71
2386
943
3.05
2670
3700
745
1.84
1630
805
2.17
1919
860
2.52
2223
909
2.87
2521
956
3.22
2807
3750
754
1.91
1691
813
2.24
1980
868
2.59
2283
917
2.95
2587
963
3.30
2870
580D090 (7
1
⁄
2
TONS)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2250
841
1.81
1604
902
2.25
1989
939
2.60
2292
2300
843
1.83
1621
905
2.28
2015
943
2.62
2309
2400
849
1.88
1665
910
2.31
2041
952
2.74
2411
2500
859
1.96
1735
912
2.31
2050
963
2.81
2470
2550
864
2.01
1779
915
2.34
2067
968
2.81
2479
2600
869
2.06
1823
918
2.37
2093
973
2.81
2487
2700
880
2.17
1919
927
2.47
2180
976
2.84
2495
2800
892
2.29
2023
938
2.58
2275
983
2.92
2562
2900
903
2.42
2136
949
2.71
2386
993
3.03
2653
3000
915
2.54
2240
961
2.85
2504
1003
3.17
2767
3100
926
2.67
2352
972
3.00
2629
1015
3.32
2886
3200
938
2.81
2470
983
3.14
2743
1026
3.47
3002
3300
950
2.95
2587
995
3.30
2870
—
—
—
3400
963
3.10
2710
1007
3.45
2987
—
—
—
3500
976
3.25
2831
—
—
—
—
—
—
3600
988
3.41
2956
—
—
—
—
—
—
3700
—
—
—
—
—
—
—
—
—
3750
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Standard drive range is 590 to 840 rpm. Alternate drive range is 685 to
935 rpm. All other rpms require a field-supplied drive.
NOTES:
1. Boldface indicates field-supplied motor and drive are required.
2. Values include losses for filters, unit casing, and wet coils. See
page 52 for accessory/FIOP static pressure information.
3. Maximum continuous bhp is 2.40 and the maximum continuous
watts are 2120. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. See Evaporator-Fan Motor Performance
table on page 55 for additional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details.
5. Interpolation is permissible. Do not extrapolate.
35