PHYSICAL DATA — 579F180-300

UNIT SIZE 579F

180

216

240

300

NOMINAL CAPACITY (tons)

15

18

20

25

OPERATING WEIGHT (lb)

Unit

Al/Al*

1650

2150

2200

2250

Economizer

110

110

110

110

Roof Curb†

200

200

200

200

COMPRESSOR

Semi-Hermetic

Model No. ...Quantity

(Number of Cylinders)

06D-537...1 (6)

06D-824...1 (6)
06D-818...1 (4)

06D-824...2 (6)

06D-328...2 (6)

Oil (oz)

115

88,115

115 ea

128 ea

No. of Cylinders (per circuit)

6

6

6

6

Cooling Capacity Stages (%)

0, 66, 100

0, 57, 100

0, 50, 100

0, 50, 100

REFRIGERANT TYPE

R-22

Expansion Device

TXV

Acutrol™ Refrigerant Metering Device

Operating Charge (lb-oz)

Circuit 1**

19-4

13-4

12-13

16-12

Circuit 2

11-0

12-13

15-12

CONDENSER COIL

3

8

-in. Enhanced Copper Tubes, Aluminum Lanced or Copper Fins

Rows...Fins/in.

2...17

3...15

3...15

4...15

Total Face Area (sq ft)

22.2

22.2

22.2

22.2

CONDENSER FAN

Propeller Type

Nominal Cfm

10,500

10,500

14,200

14,200

Quantity...Diameter (in.)

3...22

3...22

2...30

2...30

Motor Hp...Rpm

1

2

...1050

1

2

...1050

1...1075

1...1075

Watts Input (Total)

1100

1100

3400

3400

EVAPORATOR COIL

3

8

-in. Enhanced Copper Tubes, Aluminum or Copper Plate Fins, Face Split

Rows...Fins/in.

2...17

3...17

4...15

4...15

Total Face Area (sq ft)

17.9

17.9

17.9

17.9

EVAPORATOR FAN

Centrifugal Type

Quantity...Size (in.)

2...10 x 10

2...12 x 12

2...12 x 12

2...12 x 12

Type Drive

Belt

Belt

Belt

Belt

Nominal Cfm

6000

7200

8000

10,000

Motor Hp

3.7

5

7

1

2

10

Motor Nominal rpm

1725

1745

1745

1740

Maximum Continuous Bhp

4.25

5.90

8.7 [208/230 v]

9.5 [460 v]

10.2 [208/230 v]

11.8 [460 v]

Motor Frame Size

56H

184T

213T

215T

Nominal Rpm High/Low

Fan Rpm Range

Low-Medium Static

891-1179

817-1038

1002-1225

1066-1283

High Static

1227-1550

994-1197

1193-1458

1332-1550

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Allowable Rpm

1550

1550

1550

1550

Motor Pulley Pitch Diameter

Low-Medium Static

3.1-4.1

3.7-4.7

5.4-6.6

4.9-5.9

Min/Max (in.)

High Static

3.7-4.7

4.9-5.9

5.4-6.6

4.9-5.9

Nominal Motor Shaft Diameter (in.)

7

8

1

1

8

1

3

8

1

3

8

Fan Pulley Pitch Diameter (in.)

Low-Medium Static

6.0

7.9

9.4

8.0

High Static

5.2

8.6

7.9

6.4

Nominal Fan Shaft Diameter (in.)

1

3

16

1

7

16

1

7

16

1

7

16

Belt, Quantity...Type...Length (in.)

Low-Medium Static

1...BX...42

1...BX...46

1...BX...53

2...BX...50

High Static

1...BX...42

1...BX...50

1...BX...50

2...BX...47

Pulley Center Line Distance (in.)

13.5-15.5

13.3-14.8

14.6-15.4

14.6-15.4

Speed Change per Full Turn of

Low-Medium Static

48

37

37

36

Movable Pulley Flange (rpm)

High Static

55

34

44

45

Movable Pulley Maximum Full Turns

From Closed Position

5

5

5

5

Factory Setting

3.5

3.5

3.5

3.5

Factory Speed Setting (rpm)

Low-Medium Static

1035

934

1120

1182

High Static

1389

1104

1328

1470

Fan Shaft Diameter at Pulley (in.)

1

3

16

1

7

16

1

7

16

1

7

16

LEGEND

Al

Aluminum

Bhp — Brake Horsepower
Cu

Copper

TXV — Thermostatic Expansion Valve

*Evaporator coil fin material/condenser coil fin material.

†Weight of 14-in. roof curb.

**On 579F180-300 units, Circuit 1 consists of lower portion of condenser coil and

lower portion of evaporator coil, and Circuit 2 is the upper portion of both coils.

††Rollout switch lockout is manually reset by interrupting power to unit or resetting

thermostat.

The 579F300 unit requires 2-in. industrial-grade filters capable of handling face
velocities of up to 625 ft/min (such as American Air Filter no. 5700 or
equivalent).

NOTE: The 579F180-300 units have a low-pressure switch (standard) located on
the suction side.