Table 9 — Evaporator Fan Motor Data

LEGEND

BHP — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the

full horsepower range of the motors can be utilized with confidence.
Using fan motors up to the horsepower ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.

NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.

GENERAL FAN PERFORMANCE NOTES

1. Extensive motor and electrical testing on these units ensures that

the full range of the motor can be utilized with confidence. Using fan
motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.
For additional information on motor performance refer to Table 9.

2. Values include losses for filters, unit casing, and wet coils. See

Table 8 for accessory/FIOP static pressure drop information.

3. Use of a field-supplied motor may affect wire sizing. Contact your

Bryant representative for details.

4. Interpolation is permissible. Do not extrapolate.

UNIT
558F

EVAPORATOR-FAN

MOTOR

UNIT

VOLTAGE

MAXIMUM ACCEPTABLE

CONTINUOUS BHP*

MAXIMUM ACCEPTABLE

OPERATING WATTS

MAXIMUM

AMP DRAW

090,091

Standard,

Alternate

208/230

2.40

2120

6.7

460

3.0

575

3.0

High Static

208/230

3.70

3313

12.2

460

5.5

575

5.5

102,103

Standard

208/230

2.40

2120

6.7

460

3.0

575

3.0

High Static

208/230

3.70

3313

12.2

460

5.5

575

5.5

120,121

Standard

208/230

2.40

2120

6.7

460

3.0

575

3.0

Alternate

208/230

2.90

2615

8.6

460

3.9

575

3.9

High Static

208/230

5.25

4400

17.3

460

8.5

575

8.5

150,151

Standard

208/230

3.70

3313

12.2

460

5.5

575

5.5

Alternate

208/230

5.25

4400

17.3

460

8.5

575

8.5