Table 2D — Electrical Data (Units With Convenience Outlet) (558F091, 103, 121, 151)

LEGEND

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker per NEC.

**Fuse only.

††Compressor no. 1 is shown in table.

208/230-3-60: Compressor no. 2 RLA is 14.1 amps and LRA is 105 amps.
460-3-60: Compressor no. 2 RLA is 7.1 amps and LRA is 55 amps.
575-3-60: Compressor no. 2 RLA is 6.4 amps and LRA is 40 amps.

NOTES:
1.

In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.

2.

Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the
following formula to determine the percent of voltage imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility
company immediately.

3. For units with power exhaust: If a single power source is to be used, size wire to include power

exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the
unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the
power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 558FPX091000 unit with MCA = 40.1 and MOCP = 45, with
CRPWREXH030A01 power exhaust.
MCA New = 40.1 amps + 1.6 amps = 41.7 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP
in this example is 45 amps, the MCA New is below 45, therefore the MOCP is acceptable. If “MCA
New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate
power, the MOCP for the power exhaust will be 15 amps per NEC.

4. Determine heater capacity using multiplication factors table below:

NOTE: The following equation converts kW of heat energy to Btuh: kW x 3.412 = Btuh.

EXAMPLE: 32.0 kW (at 240 v) heater on 208 v

= 32.0 (.751 mult factor)
= 24.0 kW capacity at 208 v

558F
UNIT
SIZE

NOMINAL

V-PH-Hz

IFM

TYPE

VOLTAGE

RANGE

COMPRESSOR

(ea)

OFM (ea)

IFM

FLA

HEATER

MODEL NO.

CRHEATER---A00

ELECTRIC HEAT

POWER SUPPLY

DISCONNECT

SIZE*

SINGLE POINT

BOX P/N

CRSINGLE---A00

Min

Max

Qty

RLA

LRA Qty

Hp

FLA

Nominal

kW

FLA

MCA

MOCP†

FLA

LRA

091

208/230-3-60

STD

187

254

2

14

91

2

1

/

4

1.4

5.8

NONE

—/—

—/—

44.9/ 44.9

50/ 50

48/ 48

234/234

017

7.8/10.4

21.7/ 25.0

44.9/ 44.9

50/ 50

48/ 48

234/234

006

010

12.0/16.0

33.4/ 38.5

55.0/ 60.8

60/ 60

51/ 56

234/234

006

011

18.4/24.8

51.7/ 59.7

77.9/ 87.3

80/ 90**

72/ 81

234/234

007

012

24.0/32.0

66.7/ 77.0

96.6/108.9

100/110**

89/101

234/234

009

012 and 017

31.8/42.4

88.4/102.0

123.7/140.2

125/150**

114/130

234/234

009

ALT

5.8

NONE

—/—

—/—

44.9/ 44.9

50/ 50

48/ 48

234/234

017

7.8/10.4

21.7/ 25.0

44.9/ 44.9

50/ 50

48/ 48

234/234

006

010

12.0/16.0

33.4/ 38.5

55.0/ 60.8

60/ 60

51/ 56

234/234

006

011

18.6/24.8

51.7/ 59.7

77.9/ 87.3

80/ 90**

72/ 81

234/234

007

012

24.0/32.0

66.7/ 77.0

96.6/108.9

100/110**

89/101

234/234

007

012 and 017

31.8/42.4

88.4/102.0

123.7/140.2

125/150**

114/130

234/234

009

HIGH

10.6

NONE

—/—

—/—

49.7/ 49.7

60/ 60

53/ 53

277/277

017

7.8/10.4

21.7/ 25.0

49.7/ 50.0

60/ 60

53/ 53

277/277

006

010

12.0/16.0

33.4/ 38.5

61.0/ 66.8

70/ 70**

56/ 61

277/277

007

011

18.6/24.8

51.7/ 59.7

83.9/ 93.3

90/100**

77/ 86

277/277

007

012

24.0/32.0

66.7/ 77.0

102.6/114.9

110/125**

94/106

277/277

007

012 and 017

32.3/42.4

88.4/102.0

129.7/146.2

150/150**

119/135

277/277

009

460-3-60

STD

414

508

2

6.4

42

2

1

/

4

0.7

2.6

NONE

20.6

25

22

110

016

13.9

16.7

26.9

25

25

110

006

013

16.5

19.8

28.1

30

28

110

006

014

27.8

33.4

47.8

50

44

110

006

015

33.0

39.7

55.6

60

51

110

006

014 and 016

41.7

50.2

68.7

70**

63

110

008

ALT

2.6

NONE

20.6

25

22

110

016

13.9

16.7

26.9

25

25

110

006

013

16.5

19.8

28.1

30

28

110

006

014

27.8

33.4

47.8

50

44

110

006

015

33.0

39.7

55.6

60

51

110

006

014 and 016

41.7

50.2

68.7

70**

63

110

008

HIGH

4.8

NONE

22.8

25

24

132

016

13.9

16.7

29.6

30

27

132

006

013

16.5

19.8

30.8

35

31

132

006

014

27.8

33.4

50.5

60

46

132

006

015

33.0

39.7

58.3

60

54

132

006

014 and 016

41.7

50.2

71.4

80**

66

132

008

575-3-60

STD

518

632

2

5.2

39

2

1

/

4

0.7

2.6

NONE

16.6

20

18

99

018

17.0

17.1

26.1

25

24

99

006

019

34.0

34.1

47.4

45

44

99

006

ALT

2.6

NONE

16.6

20

18

99

018

17.0

17.1

26.1

25

24

99

006

019

34.0

34.1

47.4

45

44

99

006

HIGH

4.8

NONE

18.4

20

20

116

018

17.0

17.1

28.3

30

26

116

006

019

34.0

34.1

49.6

45

46

116

006

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

% Voltage Imbalance = 100 x

7

457

POWER EXHAUST

PART NO.

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for separate

power source)

CRPWREXH021A01

N/A

0.9

N/A

15

CRPWREXH022A01

3.3

N/A

1.32

15

CRPWREXH023A01

N/A

1.8

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

1.0

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

HEATER

RATING

VOLTAGE

ACTUAL HEATER VOLTAGE

200

208

230

240

380

440

460

480

550

575

600

240

0.694 0.751

0.918 1.000

480

0.626 0.840 0.918

1.000

600

0.840

0.918 1.000