12

Table 2A — Electrical Data (Units Without Convenience Outlet) (558F090, 102, 120, 150) (cont)

LEGEND

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker per NEC.

**Fuse only.

††Compressor no. 1 is shown in table.

208/230-3-60: Compressor no. 2 RLA is 14.1 amps and LRA is 105 amps.
460-3-60: Compressor no. 2 RLA is 7.1 amps and LRA is 55 amps.
575-3-60: Compressor no. 2 RLA is 6.4 amps and LRA is 40 amps.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer

to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

3. For units with power exhaust: If a single power source is to be used, size wire to include

power exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered
through the unit (must be in accordance with NEC and/or local codes). Determine the
new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 558FPX091000 unit with MCA = 40.1 and MOCP = 45, with
CRPWREXH030A01 power exhaust.
MCA New = 40.1 amps + 1.6 amps = 41.7 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change.
The MOCP in this example is 45 amps, the MCA New is below 45, therefore the MOCP is
acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next
larger size. For separate power, the MOCP for the power exhaust will be 15 amps per
NEC.

4. Determine heater capacity using multiplication factors table below:

NOTE: The following equation converts kW of heat energy to Btuh: kW x 3.412 = Btuh.

EXAMPLE: 32.0 kW (at 240 v) heater on 208 v

= 32.0 (.751 mult factor)
= 24.0 kW capacity at 208 v

558F
UNIT
SIZE

NOMINAL

V-Ph-Hz

IFM

TYPE

VOLTAGE

RANGE

COMPRESSOR

(ea)

OFM

(ea)

IFM

FLA

ELECTRIC

HEAT

POWER

SUPPLY

DISCONNECT

SIZE*

Min

Max

RLA

LRA

Qty

Hp

FLA

Nominal

kW

FLA

MCA

MOCP†

FLA

LRA

150

208/230-3-60

Std

187

254

23.0

146.0

2

1

/

4

1.4

10.6

65.2/ 65.2

80/ 80**

68/ 68

383/383

7.8/10.4

21.7/ 25.0

65.2/ 65.2

80/ 80**

68/ 68

12.0/16.0

33.4/ 38.5

65.2/ 65.2

70/ 70**

68/ 68

24.0/32.0

66.7/ 77.0

96.6/109.5

100/110**

89/101

31.8/42.4

88.4/102.0

123.7/140.8

125/150**

114/129

37.6/50.0

104.2/120.3

143.5/133.5

150/150**

132/151

Alt

15.0

69.6/ 69.6

80/ 80**

73/ 73

406/406

7.8/10.4

21.7/ 25.0

69.6/ 69.6

80/ 80**

73/ 73

12.0/16.0

33.4/ 38.5

69.6/ 69.6

80/ 80**

73/ 73

24.0/32.0

66.7/ 77.0

102.1/115.0

110/125**

94/106

31.8/42.4

88.4/102.0

129.2/146.3

150/150**

119/135

37.6/50.0

104.2/120.3

149.0/139.0

150/175**

137/156

460-3-60

Std

414

508

10.4

73.0

2

1

/

4

0.7

4.8

29.6

40

31

192

16.5

19.8

30.8

40

31

27.8

33.4

47.8

50

44

33.0

39.7

55.6

60

51

41.7

50.2

68.7

70**

63

50.0

60.1

66.1

80**

75

Alt

7.4

32.2

45

34

203

16.5

19.8

34.1

45

34

27.8

33.4

51.0

60

47

33.0

39.7

58.9

60

54

41.7

50.2

71.9

80**

66

50.0

60.1

69.4

80**

78

575-3-60

Std

518

632

8.3

58.4

2

1

/

4

0.7

4.8

23.6

30

25

154

17.0

17.1

26.1

30

25

34.0

34.1

47.5

50

44

51.0

51.2

56.0

60

63

Alt

7.4

25.7

30

27

163

17.0

17.1

28.7

35

27

34.0

34.1

50.1

60

46

51.0

51.2

58.6

70**

66

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

% Voltage Imbalance = 100 x

7

457

POWER EXHAUST

PART NO.

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for separate

power source)

CRPWREXH021A01

N/A

0.9

N/A

15

CRPWREXH022A01

3.3

N/A

1.32

15

CRPWREXH023A01

N/A

1.8

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

1.0

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

HEATER

RATING

VOLTAGE

ACTUAL HEATER VOLTAGE

200

208

230

240

380

440

460

480

550

575

600

240

0.694 0.751 0.918 1.000

480

0.626 0.840 0.918 1.000

600

0.840 0.918 1.000