beautypg.com

Bryant DURAPACK 558F User Manual

Page 21

background image

21

Table 2D — Electrical Data (Units With Convenience Outlet) (558F091, 103, 121, 151) (cont)

LEGEND

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker per NEC.

**Fuse only.

††Compressor no. 1 is shown in table.

208/230-3-60: Compressor no. 2 RLA is 14.1 amps and LRA is 105 amps.
460-3-60: Compressor no. 2 RLA is 7.1 amps and LRA is 55 amps.
575-3-60: Compressor no. 2 RLA is 6.4 amps and LRA is 40 amps.

NOTES:
1.

In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.

2.

Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the
following formula to determine the percent of voltage imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility
company immediately.

3. For units with power exhaust: If a single power source is to be used, size wire to include power

exhaust MCA and MOCP. Check MCA and MOCP when power exhaust is powered through the
unit (must be in accordance with NEC and/or local codes). Determine the new MCA including the
power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 558FPX091000 unit with MCA = 40.1 and MOCP = 45, with
CRPWREXH030A01 power exhaust.
MCA New = 40.1 amps + 1.6 amps = 41.7 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The MOCP
in this example is 45 amps, the MCA New is below 45, therefore the MOCP is acceptable. If “MCA
New” is larger than the published MOCP, raise the MOCP to the next larger size. For separate
power, the MOCP for the power exhaust will be 15 amps per NEC.

4. Determine heater capacity using multiplication factors table below:

NOTE: The following equation converts kW of heat energy to Btuh: kW x 3.412 = Btuh.

EXAMPLE: 32.0 kW (at 240 v) heater on 208 v

= 32.0 (.751 mult factor)
= 24.0 kW capacity at 208 v

558F
UNIT
SIZE

NOMINAL

V-PH-Hz

IFM

TYPE

VOLTAGE

RANGE

COMPRESSOR

(ea)

OFM (ea)

IFM

FLA

HEATER

MODEL NO.

CRHEATER---A00

ELECTRIC HEAT

POWER SUPPLY

DISCONNECT

SIZE*

SINGLE POINT

BOX P/N

CRSINGLE---A00

Min

Max

Qty

RLA

LRA

Qty

Hp

FLA

Nominal

kW

FLA

MCA

MOCP†

FLA

LRA

151

208/230-3-60

STD

187

254

2

19

156

2

1

/

4

1.4

10.6

NONE

—/—

—/—

61.0/ 61.0

70/ 70**

65/ 65

364/364

017

7.8/10.4

21.7/ 25.0

61.0/ 61.0

70/ 70**

65/ 65

364/364

012

010

12.0/16.0

33.4/ 38.5

61.0/ 66.8

70/ 70**

65/ 65

364/364

012

012

24.0/32.0

66.7/ 77.0

102.6/114.9

110/125**

94/106

364/364

012

012 and 017

31.8/42.4

88.4/102.0

129.7/146.2

150/150**

119/135

364/364

015

010 and 012

37.6/50.0

104.2/120.3

149.6/169.0

150/175**

138/156

364/364

015

ALT

15

NONE

—/—

—/—

65.4/ 65.4

80/ 80**

70/ 70

383/383

017

7.8/10.4

21.7/ 25.0

65.4/ 65.4

80/ 80**

70/ 70

383/383

012

010

12.0/16.0

33.4/ 38.5

66.5/ 72.3

80/ 80**

70/ 70

383/383

012

012

24.0/32.0

66.7/ 77.0

108.1/120.4

110/125**

99/111

383/383

012

012 and 017

31.8/42.4

88.4/102.0

135.2/151.7

150/175**

124/140

383/383

015

010 and 012

37.6/50.0

104.2/120.3

155.1/174.5

175/175**

143/161

383/383

015

460-3-60

STD

414

508

2

9

75

2

1

/

4

0.7

4.8

NONE

28.7

35

30

176

013

16.5

19.8

33.5

35

31

176

011

014

27.8

33.4

47.8

45

46

176

011

015

33.0

39.7

58.3

60

54

176

011

014 and 016

41.7

50.2

71.4

80**

66

176

014

013 and 015

50.0

60.1

83.9

90**

77

176

014

ALT

7.4

NONE

31.3

35

33

215

013

16.5

19.8

36.8

40

34

215

011

014

27.8

33.4

51.0

60

49

215

011

015

33.0

39.7

61.6

70**

57

215

014

014 and 016

41.7

50.2

74.7

80**

69

215

014

013 and 015

50.0

60.1

87.1

90**

80

215

014

575-3-60

STD

518

632

2

7.4

54

2

1

/

4

0.7

4.8

NONE

23.3

30

25

129

018

17.0

17.1

28.3

30

26

129

011

019

34.0

34.1

49.6

45

46

129

011

018 and 019

51.0

51.2

71.0

80**

65

129

014

ALT

7.4

NONE

25.4

30

27

160

018

17.0

17.1

30.9

35

28

160

011

019

34.0

34.1

52.2

50

48

160

011

018 and 019

51.0

51.2

73.6

80**

68

160

014

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

% Voltage Imbalance = 100 x

7

457

POWER EXHAUST

PART NO.

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for separate

power source)

CRPWREXH021A01

N/A

0.9

N/A

15

CRPWREXH022A01

3.3

N/A

1.32

15

CRPWREXH023A01

N/A

1.8

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

1.0

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

HEATER

RATING

VOLTAGE

ACTUAL HEATER VOLTAGE

200

208

230

240

380

440

460

480

550

575

600

240

0.694 0.751

0.918 1.000

480

0.626 0.840 0.918

1.000

600

0.840

0.918 1.000