beautypg.com

Fig. 12—two-stage control – Bryant 352MAV User Manual

Page 9

background image

NOTE:

Heat tape, when used, should be wrapped around the

condensate drain trap and drain line. There is no need to use heat
tape within the furnace casing. Most heat tapes are temperature
activated, and it is not practical to verify the actual heating of the
tape. Check the following:

1. Check for signs of physical damage to heat tape such as

nicks, cuts, abrasions, gnawing by animals, etc.

CAUTION:

If this furnace is installed in an uncondi-

tioned space where the ambient temperatures may be
32°F or lower, freeze protection measures must be taken.

2. Check for discolored heat tape insulation. If any damage or

discolored insulation is evident, replace heat tape.

3. Check that heat tape power supply circuit is on.

IX.

WINTERIZING

CAUTION:

Freezing condensate left in the furnace will

damage the equipment.

If the furnace will be off for an extended period of time in a
structure where the temperature will drop to 32° or below,
winterize as follows:

1. Turn off electrical supply to furnace.

2. Remove main furnace door.

3. Disconnect cap from unused drain tap on inducer housing.

(See Fig. 13.)

4. Insert funnel in drain tube and pour antifreeze, propylene

glycol (RV, swimming pool antifreeze, or equivalent) into
furnace until it is visible at point where condensate enters
open drain. (See Fig. 14.)

5. Reconnect drain tube to inducer housing.

6. Replace main furnace door.

CAUTION:

Do not use ethylene glycol (Prestone II

antifreeze/coolant or equivalent automotive type). Failure
of plastic components will occur.

WIRING DIAGRAM

See Fig. 15 for Wiring Diagram

TROUBLESHOOTING

Use the Troubleshooting Guide, the status code LED on the control
and the Component Test to isolate furnace operation problems.

I.

STATUS CODES

For an explanation of status codes, refer to service label located on
back of main furnace door or Fig. 16. The control will store up to
5 previous codes but will not store a non-current code longer than
48 hours.

NOTE:

Removing the blower access door will open the blower

access door switch and terminate 115-v power to the control is
interrupted.
To read current status code, remove main furnace door. The status
code LED can be viewed through the sight glass on the blower
access door.

NOTE:

NO thermostat signals may be present at control and all

blower off delays must be expired to view previous codes.
To retrieve previous codes, remove 1 of the red main limit wires
1 to 4 sec until the LED light goes out, then reconnect it. (Do not
leave red wire disconnected for longer periods of time as the
control will assume an overtemperature condition exits and will
respond with blower operation.) This places the control in the
status recall mode and displays the first code stored in memory
Record the code and repeat the disconnect and reconnect of the red
wire, recording each code until code 11 is displayed indicating no
additional faults. After the last code is displayed or after 2 minutes
in the code, recall mode the control will return to normal standby
mode.

II.

COMPONENT TEST

Use the Component Test to check furnace components for proper
operation. To initiate the component self-test sequence, shut off
the room thermostat or disconnect the “R”thermostat lead. Briefly
(approx. 2 sec) short the TWIN/TEST terminal to the C

OM

24V

terminal. The status LED will turn off. The test sequence will be
as follows:

A93058

32

°

F MINIMUM INSTALLED

AMBIENT OR FREEZE
PROTECTION REQUIRED

Fig. 12—Two-Stage Control

A93348

1

2

3

4

5

6

7

8

9

PR2

L2

COM

PR1

L1

EAC-2

EAC-1

H

I-

COO

L

HI-GAS

-HEAT

LO-GAS

-HEAT

PARK

3

FU1

SEC-1

SEC-2

1

1

2

3

4

5

6

7

8

9

10

11

12

MASTER SLAVE

TWIN

TEST

LED

G

R

Y/Y2

W/W1

COM

24 V

W2

1

ON

OFF

1

2

3

4

FURNACE AND
BLOWER OFF DELAY
SETUP SWITCHES

24-VOLT
THERMOSTAT
TERMINALS

EAC - ELECTRONIC

AIR CLEANER

(115-VAC 1 AMP MAX)

3-AMP
FUSE

LED -
DIAGNOSTIC
LIGHT

TWIN / TEST
TERMINAL

HUM -
HUMIDIFIER
(24-VAC 0.5
AMP MAX)

HUM

—9—