8. Remove manifold, orifices, and gas valve as 1 assembly.

9. Remove screws attaching burner assembly in burner box.

10. Remove burner assembly from burner box.

NOTE:

All burners are attached to burner bracket and can be

removed as 1 assembly.

11. Clean burners with soft brush and vacuum.

12. Reinstall manifold, orifice, and gas valve assembly in

burner box. Ensure manifold seal grommet is installed
properly and burners fit over orifices.

13. Reconnect wires to gas valve. Refer to furnace wiring

diagram for proper wire location.

14. Reinstall burner box pressure tube to gas valve regulator

fitting.

15. Reinstall gas supply pipe to gas valve using backup wrench

on gas valve to prevent rotation and improper orientation.

NOTE:

Use propane gas resistant pipe dope to prevent gas leaks.

DO NOT use Teflon tape.

WARNING:

Gas valve switch or knob MUST be facing

forward or tilted upward. Failure to follow this warning
could result in property damage, personal injury, or death.

16. Replace burner box cover.

17. Turn on gas and electrical supplies to furnace.

18. Check for gas leaks.

WARNING:

Never use matches, candles, flame, or

other sources of ignition to check for gas leakage. Use a
soap-and-water solution. Failure to follow this warning
could result in a fire, personal injury, or death.

19. Replace main furnace door.

IV.

CLEANING HEAT EXCHANGERS

The following items should be performed by a qualified service
technician.

A.

Primary Heat Exchangers

If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:

NOTE:

If the heat exchangers get a heavy accumulation of soot

and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build-up of soot and carbon indicates
that a problem exists which needs to be corrected, such as
improper adjustment of manifold pressure, insufficient or poor
quality combustion air, improper vent termination, incorrect size
or damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.

1. Turn off gas and electrical supplies to furnace.

2. Remove main furnace door.

CAUTION:

Label all wires prior to disconnection when

servicing controls. Wiring errors can cause improper and
hazardous operation.

3. Disconnect wires or connectors to rollout switch, gas valve,

ignitor, and flame sensor.

4. Disconnect combustion-air intake pipe from intake housing.

5. Remove the pressure switch tube from intake housing.

6. Remove screws attaching intake housing to burner box, and

rotate intake housing away from burner box for removal.

7. Using backup wrench, disconnect gas supply pipe from gas

valve.

8. Disconnect pressure tubing from gas valve.

9. Remove 2 screws attaching top filler panel and rotate

upwards to gain access to screws attaching burner box to
cell panel.

10. Remove screws attaching burner box to cell panel. (See Fig.

5.)

NOTE:

Burner box cover, manifold, gas valve, and burner

assembly should be removed as 1 assembly.

11. Clean heat exchanger openings with a vacuum and a soft

brush. (See Fig. 6.)

NOTE:

After cleaning, inspect the heat exchangers to ensure they

are free of all foreign objects that may restrict flow of combustion
products.

12. Reverse items 4 through 10 for reassembly.

WARNING:

The ground wire from the gas valve MUST

be attached to the burner box attachment screw. Failure to
attach this ground wire to an adequate casing ground will
cause the furnace control to lock out.

NOTE:

Be sure burner box gasket is installed between burner box

and cell panel. If gasket is damaged, replace it.

Fig. 6—Cleaning Inlet Openings of Primary Heat

Exchangers

A96305

PRIMARY HX
INLET OPENINGS

Fig. 7—Combustion-Air Intake Housing Gasket Repair

A93087

PAM

RTV