beautypg.com

Bryant 355MAV EN User Manual

Page 42

background image

B.

Set Temperature Rise

CAUTION:

Temperature rise must be within limits

specified on unit rating plate. Recommended operation is
at midpoint of rise or above. Failure to follow this caution
may result in condensing or overheating the heat ex-
changers.

Furnace must operate within range of temperature rise specified on
the unit rating plate. Determine air temperature rise as follows:

1. Place thermometers in return and supply ducts as near

furnace as possible. Be sure thermometers do not see heat
exchanger so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.

2. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine air
temperature rise.

NOTE:

Temperature rise can be determined for low-fire opera-

tion by placing setup switch SW-2 on control center in ON
position. For high-heat operation, place setup switch SW-2 in OFF
position and jumper R-W2 on control center. DO NOT forget to
return setup switch to OFF position and remove R-W2 jumper
upon completion of testing. (See Fig. 25 for switch and terminal
location.)

3. This furnace is capable of automatically providing proper

airflow to maintain the temperature rise within the range
specified on unit rating plate. If temperature rise is outside
this range, proceed as follows:
a. Check gas input for low- and high-heat operation.

b. Check derate for altitude if applicable.

c. Check all return and supply ducts for excessive restric-

tions causing static pressure greater than 0.5-in. wc.

d. Ensure bypass humidifier switch (BPH) setup switch

SW-3 on control center is in ON position when a bypass
humidifier is used. (See Fig. 25 for switch location.)

e. Check

Troubleshooting

Guide

for

Variable-Speed

2-Stage Electronic Condensing Furnaces.

C.

Set Thermostat Heat Anticipator

The thermostat heat anticipator must be set to match the amp draw
of components in the R-W/W1 circuit. Accurate amp draw
measurements can be obtained at the thermostat subbase terminals
R and W.

Fig. 50 illustrates an easy method of obtaining thermostat amp
draw measurements. The amp reading should be taken after blower
motor has started and furnace is operating in low heat.

1. To operate furnace in low heat, turn setup switch SW-2 to

ON position (See Fig. 25) and connect ammeter leads
across thermostat subbase R-W.

2. See thermostat manufacturer’s instructions for adjusting the

heat anticipator and for varying heating cycle length.

NOTE:

When using an electronic thermostat, set cycle rate for 3

cycles per hr.

3. Return setup switch SW-2 to OFF position and replace

thermostat on subbase.

CHECK SAFETY CONTROLS

I.

CHECK PRIMARY LIMIT CONTROL

This control shuts off the combustion control system and energizes
the air-circulating blower motor if furnace overheats.

1. The recommended method of checking this limit control is

to gradually block off return air after furnace has been
operating for a period of at least 5 minutes.

2. As soon as limit control has shut off burners, a 33 fault code

will appear on control center.

3. The return-air opening should be unblocked to permit

normal air circulation.

By using this method to check the limit control, it can be
established that the limit is functioning properly and the furnace
will operate safely if there is a restricted return-air supply or motor
failure. If the limit control does not function during this test, the
cause must be determined and corrected.

TABLE 14—GAS RATE CU FT/HR

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

1

cu ft

2

cu ft

5

cu ft

1

cu ft

2

cu ft

5

cu ft

10
11
12
13
14

360
327
300
277
257

720
655
600
555
514

1800
1636
1500
1385
1286

50
51
52
53
54

72
71
69
68
67

144
141
138
136
133

360
355
346
340
333

15
16
17
18
19

240
225
212
200
189

480
450
424
400
379

1200
1125
1059
1000

947

55
56
57
58
59

65
64
63
62
61

131
129
126
124
122

327
321
316
310
305

20
21
22
23
24

180
171
164
157
150

360
343
327
313
300

900
857
818
783
750

60
62
64
66
68

60
58
56
54
53

120
116
112
109
106

300
290
281
273
265

25
26
27
28
29

144
138
133
129
124

288
277
267
257
248

720
692
667
643
621

70
72
74
76
78

51
50
48
47
46

103
100

97
95
92

257
250
243
237
231

30
31
32
33
34

120
116
113
109
106

240
232
225
218
212

600
581
563
545
529

80
82
84
86
88

45
44
43
42
41

90
88
86
84
82

225
220
214
209
205

35
36
37
38
39

103
100

97
95
92

206
200
195
189
185

514
500
486
474
462

90
92
94
96
98

40
39
38
38
37

80
78
76
75
74

200
196
192
188
184

40
41
42
43
44

90
88
86
84
82

180
176
172
167
164

450
439
429
419
409

100
102
104
106
108

36
35
35
34
33

72
71
69
68
67

180
178
173
170
167

45
46
47
48
49

80
78
76
75
73

160
157
153
150
147

400
391
383
375
367

110
112
116
120

33
32
31
30

65
64
62
60

164
161
155
150

Fig. 50—Amp Draw Check with Ammeter

A96316

R

Y W G

10 TURNS

THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)

HOOK-AROUND
AMMETER

EXAMPLE:

5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS

=

0.5 AMPS FOR THERMOSTAT

ANTICIPATOR SETTING

FROM UNIT 24-V
CONTROL TERMINALS

—42—