Bryant 355MAV EN User Manual

Page 36

background image

TABLE 10—SETUP SWITCH DESCRIPTION

SETUP

SWITCH NO.

NORMAL

POSITION

DESCRIPTION OF USE

SW-1
(FLT)

OFF

Turn switch to ON for fault history display. No thermostat signal can be
present for fault history display.

SW-2

(LOW)

OFF

Turn switch to ON to lock furnace in low-heat mode only.

SW-3

(BPH)

OFF

Turn switch to ON when a bypass humidifier is used. This compensates
for higher return-air temperature and provides 5 percent more airflow in
low-heat mode only.

SW-4

(EMER HEAT)

OFF

Turn switch to ON to bypass microprocessor control. Furnace will oper-
ate at high heat only with main blower and inducer motor operating at
maximum RPM. NO safeties are bypassed.

SW-5

(MZ)

OFF

Turn switch to ON when modulating dampers are used. In this mode,
main blower speed is recalculated once every minute while furnace is in
low-heat or continuous fan mode.

SW-6

(COMP TEST)

OFF

Turn switch to ON to initiate component test. Furnace will operate in-
ducer motor for 20 sec at low speed, operate inducer motor for 20 sec at
high speed, energize HSI for 15 sec, operate blower for 20 sec at low
speed, and operate blower for 20 sec at high speed. SW-1 must be in
OFF position. No thermostat signal can be present for component test to
be initiated.

SW-7 and -8

(Blower Off Delay)

See Table 11

Adjust switches to provide desired heating mode blower off delay time,
90, 135, 180, or 225 sec.

TABLE 11—BLOWER OFF DELAY SETUP SWITCH

POSITION

DESIRED HEATING

MODE BLOWER

OFF DELAY (SEC)

SETUP SWITCH (SW-7 AND -8) POSITION

SW-7

SW-8

90

OFF

OFF

135

ON

OFF

180

OFF

ON

225

ON

ON

Fig. 46—Inducer Housing Drain Tube

A94208

Fig. 47—Filling Condensate Trap

A94209

—36—