beautypg.com

Bryant 355MAV EN User Manual

Page 18

background image

NOTE:

Proper polarity must be maintained for 115-v wiring. If

polarity is incorrect, control center fault code indicator light will
flash rapidly and furnace will NOT operate.

WARNING:

The cabinet MUST have an uninterrupted

or unbroken ground according to NEC ANSI/NFPA
70-1996 and Canadian Electrical Code CSA C22.1 or
local codes to minimize personal injury if an electrical
fault should occur. This may consist of electrical wire or
conduit approved for electrical ground when installed in
accordance with existing electrical codes. Do not use gas
piping as an electrical ground. Failure to follow this
warning could result in electric shock, fire, or death.

J-BOX RELOCATION

1. Remove 2 screws holding auxiliary J-box. (See Fig. 23.)

2. Rotate J-box 180° and attach box to right side, using holes

provided.

CAUTION:

If manual disconnect switch is to be

mounted on furnace, select a location where a drill or
fastener will not contact electrical or gas components.

II.

24-V WIRING

Make field 24-v thermostat connections at 24-v terminal block on
control center. Y wire from thermostat MUST be connected to Y
terminal on control center, as shown in Fig. 22, for proper cooling
operation. The 24-v terminal board is marked for easy connection
of field wiring. (See Fig. 24.) The 24-v circuit contains a 3-amp,
automotive-type fuse located on control center. (See Fig. 25.) Any
electrical shorts of 24-v wiring during installation, service, or
maintenance may cause fuse to blow. If fuse replacement is
required, use only a fuse of identical size (3 amp).

Fig. 22—Heating and Cooling Application Wiring Diagram

A96338

115-VOLT

FUSED

DISCONNECT

SWITCH

(WHEN REQUIRED)

115-VOLT

SINGLE

PHASE

AUXILIARY
J-BOX

FURNACE

CONTROL

CENTER

TWO WIRE

24-VOLT
TERMINAL
BLOCK

THREE-WIRE

HEATING

ONLY

FIVE

WIRE

NOTE 5

NOTE 1

NOTE

3

THERMOSTAT
TERMINALS

FIELD-SUPPLIED

FUSED DISCONNECT

CONDENSING

UNIT

R

W2

W

C

R

G

Y

GND

GND

GND

GND

FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-, 208/230-, 460-VOLT WIRING

208/230- OR
460-VOLT
THREE
PHASE

208/230-
VOLT
SINGLE
PHASE

W/W1

Y/Y2

G

C

NOTES:

1.
2.
3.
4.

5.

Connect Y or Y/Y2 terminal as shown for proper cooling operation.
Proper polarity must be maintained for 115-volt wiring.
Use W2 with 2-stage thermostat when zoning.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
Some thermostats require a "C" terminal connection as shown.

CAUTION:

Do not connect aluminum wire between

disconnect switch and furnace. Use only copper wire.

A93033

COPPER

WIRE ONLY

ELECTRIC

DISCONNECT

SWITCH

ALUMINUM

WIRE

Fig. 23—Relocating J-Box

A93051

ALTERNATE
FIELD
LOCATION

FACTORY

INSTALLED

LOCATION

—18—