beautypg.com

Bryant 355MAV EN User Manual

Page 28

background image

contaminants, and has less visible vent vapors. (See Fig. 31 or 32.)
Sidewall termination may require sealing or shielding of building
surfaces with a corrosive resistance material due to corrosive
combustion products of vent system.

A.

Extended Exposed Sidewall Pipes

Sidewall combustion-air and vent pipe terminations may be
extended beyond area shown in Fig. 34 or 35 in outside ambient by
insulating pipes as indicated in Table 7.

1. Determine combustion-air and vent pipe diameters, as

stated above, using total pipe length and number of elbows.

2. Using winter design temperature (used in load calculations),

find appropriate temperature for your application and fur-
nace model.

3. Determine required insulation thickness for exposed pipe

lengths.

NOTE:

Pipe length (ft) specified for maximum pipe lengths

located in unconditioned spaces cannot exceed total allowable pipe
length as specified in Table 6.

B.

Two-Pipe Termination Kit

1. Determine location for termination.

Consideration of the following should be made when
determining an appropriate location for termination kit.
a. Comply with all clearance requirements as stated in

Table 5.

b. Termination kit should be positioned where vent vapors

will not damage plants/shrubs or air conditioning equip-
ment.

c. Termination kit should be positioned so it will not be

affected by wind eddy (such as inside building corners)
or accumulation of airborne leaves or light snow, or
allow recirculation of flue gases.

d. Termination kit should be positioned where it will not be

damaged by or subjected to foreign objects, such as
stones, balls, etc.

e. Termination kit should be positioned where vent vapors

are not objectionable.

2. Cut 2 holes, 1 for each pipe, of appropriate size for pipe size

being used.

3. Loosely install elbow in bracket and place assembly on

combustion-air pipe.

Roof terminations—Loosely install pipe coupling on prop-
erly cut vent pipe. Coupling must be positioned so bracket
will mount as shown in Fig. 31.

For applications using combustion-air pipe option indicated
by dashed lines in Fig. 31, install 90° street elbow into 90°
elbow, making U-fitting. A 180° U-fitting may be used.

Sidewall terminations—Install bracket as shown in Fig. 34
or 35.

For applications using vent pipe option indicated by dashed
lines in Fig. 34, rotate vent elbow 90° from position shown
in Fig. 34.

4. Disassemble loose pipe fittings. Clean and cement using

same procedures as used for system piping.

5. Check required dimensions as shown in Fig. 31, 34, or 35.

C.

Concentric Vent/Air Termination Kit

1. Determine location for termination.

Consideration of the following should be made when
determining an appropriate location for termination kit.

a. Comply with all clearance requirements as stated in

Table 5.

b. Termination kit should be positioned where vent vapors

will not damage plants/shrubs or air conditioning equip-
ment.

c. Termination kit should be positioned so it will not be

affected by wind eddy (such as inside building corners)
or accumulation of airborne leaves or light snow, or
allow recirculation of flue gases.

d. Termination kit should be positioned where it will not be

damaged by or subjected to foreign objects, such as
stones, balls, etc.

e. Termination kit should be positioned where vent vapors

are not objectionable.

2. Cut one 4-in. diameter hole for 2-in. kit, or one 5-in.

diameter hole for 3-in. kit.

3. Loosely assemble concentric vent/air termination compo-

nents together using instructions in kit.

4. Slide assembled kit with rain shield REMOVED through

hole.

TABLE 7—MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH INSULATION IN WINTER DESIGN

TEMPERATURE AMBIENT*

UNIT

SIZE

WINTER DESIGN

TEMPERATURE

(°F)

MAXIMUM PIPE

DIAMETER

(IN.)

INSULATION THICKNESS (IN.)†

0

3/8

1/2

3/4

1

042040

20

2

21

37

42

50

57

0

2

10

22

25

30

35

-20

2

5

14

17

21

25

042060

20

2

30

55

61

70

70

0

2

16

33

38

46

53

-20

2

9

23

26

33

38

042080
060080

20

2

37

65

70

70

70

0

2

20

39

45

55

63

-20

2

11

27

31

39

45

060100

20

2-1/2

41

70

70

70

70

0

2-1/2

21

42

48

59

68

-20

2-1/2

11

28

33

41

49

060120

20

3

49

70

70

70

70

0

3

26

51

58

70

70

-20

3

15

35

40

50

59

* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as

specified in Table 6.

† Insulation thickness based on R value of 3.5 per in.

—28—